FIG 55. ELECTRICAL CONNECTIONSConnections to the Module are via plug and sockets.5.1 CONNECTION DETAILSThe following describes the connections and recommended cable sizes to the 6 plugs and socketson the rear of the Module. See rear panel layout FIG 5.PLUG “A” 18 WAYPIN DESCRIPTION CABLENOTESNoSIZE*1 Oil Pressure sender +ve 0.5mm or digital pressure switch connection.2 Oil Pressure sender -ve 0.5mm3 Oil Pressure sender -ve 0.5mm for use with insulated return type sendersfeed4 Fuel level sender +ve 0.5mm or digital fuel level switch connection5 Fuel level sender -ve 0.5mm6 Fuel level sender -ve feed 0.5mm for use with insulated return type senders7 Engine Coolant Temp. +ve 0.5mm or digital temperature switch input8 Engine Coolant Temp. -ve 0.5mm9 Engine Coolant Temp. -ve 0.5mm for use with insulated return type sendersfeed10 Engine Oil Temp. +ve 0.5mm or digital temperature switch input11 Engine Oil Temp. -ve 0.5mm12 Engine Oil Temp. -ve feed 0.5mm for use with insulated return type senders13 DO NOT USE Ensure no connection is made to this pin14 Generator CT on L1 2.5mm Do not fit resistors to CT’s15 Generator CT on L2 2.5mm if single phase then not used16 Generator CT on L3 2.5mm if single phase then not used17 CT common if Neutral CT 2.5mm only use if neutral CT fittedfitted18 Neutral CT if fitted 2.5mm If no neutral CT fitted use as CT commonPLUG “B” 15 WAYPIN DESCRIPTION CABLENOTESNoSIZE*19 Output 8 Normally closed 0.5mm Normally spare auxiliary output unless usingbreaker control. Then used for mains ACBclose connection20 Output 8 Common0.5mm “ “ “connection21 Output 8 Normally open 0.5mm “ “ “22 DO NOT USE Ensure no connection is made to this pin23 Output 7 Normally closed 0.5mm Normally spare auxiliary output unless usingbreaker control. Then used for mains shunttrip or UV coil feed.24 Output 7 Common0.5mm “ “ “connection25 Output 7 Normally open 0.5mm “ “ “26 DO NOT USE Ensure no connection is made to this pin.27 Output 6 Normally closed 0.5mm Normally Generator contactor control unlessusing breaker control. Then used forgenerator ACB close connection28 Output 6 Commonconnection0.5mm “ “ “20606 OPERATING MANUAL ISSUE 2 11/27/00 MR
29 Output 6 Normally open 0.5mm “ “ “606 OPERATING MANUAL ISSUE 2 11/27/00 MR21
- Page 1 and 2: Deep Sea Electronics PlcMODEL 606OP
- Page 3 and 4: 9. TYPICAL WIRING DIAGRAM..........
- Page 5 and 6: 1. OPERATION1.1 CONTROLControl of t
- Page 7 and 8: attempts to start have been complet
- Page 9 and 10: BATTERY HIGH VOLTAGE, if the module
- Page 11 and 12: AUXILIARY INPUTS, if an auxiliary i
- Page 13 and 14: NOTE:- If the following screen is d
- Page 15 and 16: This LED indicates that the module
- Page 17 and 18: i.e.:-Display shows:-EMERGENCY STOP
- Page 19: 4.4 FRONT PANEL LAYOUT4.5 REAR PANE
- Page 23 and 24: PLUG “E” 20 WAYPIN DESCRIPTION
- Page 25 and 26: 5.2 CONNECTOR FUNCTION DETAILSThe f
- Page 27 and 28: PLUG “E” 20 WAYPIN DESCRIPTIONN
- Page 29 and 30: 6. SPECIFICATIONDC Supply8.0 to 35
- Page 31 and 32: 8. FAULT FINDINGSYMPTOMPOSSIBLE REM