TR_CRITICAL_IO Function Block 77Parameter Type DescriptionOutputs ERROR DINT Error Number:0 = No error-1 = Slot is not odd or notnumbered 1–15-2 = Invalid chassis or slot-3 = Module not configured-4 = Reserved (not used)-5 = Invalid applicationnumber-6 = Not initializedRuntime Error Code Return Value ConditionEBADPARAMBad parameterNote If there is a programming error, then CO is false and the error number isnon-zero. For more information, see ERROR above.App Relay_OK DescriptionRELAY True A single fault (even a voter fault) degrades themode to dual. The relay provides a third channelfor shutdown so that if an output voter fails,there remain two independent channels (therelay and other output voter channel) that cande-energize the output.RELAY False A voter fault degrades the mode to single. ADE-ENERGIZED —non-voter fault degrades the mode to dual.AttributeApplication TypeProgramming UsageCEM FeatureUsage<strong>Safety</strong>, ControlN/AN/ALibrary<strong>Tricon</strong>Appendix APeer-to-Peer Communication