13.07.2015 Views

Safety Considerations Guide, Tricon v9.0 - Tuv-fs.com

Safety Considerations Guide, Tricon v9.0 - Tuv-fs.com

Safety Considerations Guide, Tricon v9.0 - Tuv-fs.com

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

98 TR_CRITICAL_IO Function BlockParameter Type DescriptionOutputs ERROR DINT Error Number:0 = No error-1 = Slot is not odd or notnumbered 1–15-2 = Invalid chassis or slot-3 = Module not configured-4 = Reserved (not used)-5 = Invalid applicationnumber-6 = Not initializedRuntime Error Code Return Value ConditionEBADPARAMBad parameterNote If there is a programming error, then CO is false and the error number isnon-zero. For more information, see ERROR above.App Relay_OK DescriptionRELAY True A single fault (even a voter fault) degrades themode to dual. The relay provides a third channelfor shutdown so that if an output voter fails,there remain two independent channels (therelay and other ouput voter channel) that can deenergizethe output.RELAY False A voter fault degrades the mode to single. ADE-ENERGIZED —non-voter fault degrades the mode to dual.AttributeApplication TypeProgramming UsageCEM FeatureUsage<strong>Safety</strong>, ControlN/AN/ALibrary<strong>Tricon</strong><strong>Tricon</strong> <strong>Safety</strong> <strong>Considerations</strong> <strong>Guide</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!