2011 <strong>KEPIC</strong>-Week, JejuRd Reduction FactorFlange widthb b 1 if Type "SLBB"b 8inb 2 if Type "LLBB"From <strong>AISC</strong> LRFD Appendix B-5.3a (a), reduction factor Q can be obtained asfollowsQ b1 if 0.45EQ 0.912t F yotherwise1.340 0.76b t F yEbif 0.91tEF y0.53E2otherwisebF y t HomeCritical Buckling StressFrom <strong>AISC</strong> LRFD-Appendix B-5 3d, the critical stress F cr is determined asfollowsF cr Q 0.658 Q 2 e Fy if e Q 1.5F cr 22.46ksi0.877F y otherwise2 eDesign StrengthCheckP n F cr A 2gP d c F cr A 2gP d 221.46kips P u 200kipsCheck "This section is O.K." if P u P d"N.G. Select a section again." otherwiseHomeCheck "This section is O.K."Structures Lab. Department of Civil Engineering, Hongik University2011 <strong>KEPIC</strong>-Week, Jeju Structures Lab. Department of Civil Engineering, Hongik University- 31 -