.cAnnexImportant <strong>DALI</strong> parameters and <strong>DALI</strong> commandsTable: Important <strong>DALI</strong> ballast parameters<strong>DALI</strong> parameterActual LevelMaximum LevelMinimum LevelPower ON LevelSystem FailureLevelFade TimeFade RateScene registers1-16Group registerDescriptionCurrent brightness value of the ballastMaximum brightness value – this value cannot be exceeded when fading upMinimum brightness value – this value cannot be undershot when fading downBrightness value to which the <strong>DALI</strong> ballast switches when the power supply is switched on.Brightness value to which the <strong>DALI</strong> ballast switches when a fault is detected in the <strong>DALI</strong> circuit(e.g. interruption or short-circuit on the <strong>DALI</strong> line)Time in seconds for fading from the current brightness value to the new brightness value (forDAP commands and scene calls)Fade steps per second that are performed in response to an indirect fade command (Up andDown commands)These registers are where the brightness values for the individual scenes are stored.This register is where the group assignment of the <strong>DALI</strong> ballast is stored.<strong>DALI</strong> Manual | 08-2013 | en87 / 93