.cDesigning a <strong>DALI</strong> applicationOpen-plan officeApplicationOffice with 6 workstations plus cabinets.Each desk has 2 workstations.RequirementThe lighting consists of 3 rows of luminaires, 2 rows above the workstations and 1 in the walkway and cabinet area.The requirements for control are as follows:On/off switching via motion sensorsDaylight-dependent control of illuminanceManual control via <strong>DALI</strong> TOUCHPANELFigure: Installation for Open-plan office without wiringSolution with <strong>DALI</strong> MSensor 02The room is divided into 4 groups, 3 for the workstation islands and 1 for walkway and cabinet area lighting. The 3groups for the workstation islands are each controlled with a <strong>DALI</strong> MSensor 02. The fourth group is controlled with 3<strong>DALI</strong> MSensor 02 (increased presence detection area).Each workstation island and the walkway lighting is independently controlled (presence detection and ambient lightcontrol).<strong>DALI</strong> Manual | 08-2013 | en67 / 93