7 Networking M3000 ® Modules Networking DIN Rail Modules<br />

7.7.2.1 Examples<br />

Master Slave Slave Slave<br />

<strong>MSC</strong> <strong>II</strong><br />

WCAN<br />

Figure 46: E-Bus Group (<strong>MSC</strong> <strong>II</strong> as E-Bus Master)<br />

Number of slaves that may be attached to the <strong>MSC</strong> <strong>II</strong>:<br />

�-Table-12 on page 61<br />

Master<br />

RDIO<br />

CAN<br />

Slave<br />

QDIO<br />

QAIO QAIO QDIO<br />

Slave<br />

QDIO<br />

Slave<br />

QDIO<br />

Figure 47: E-Bus Group (RDIO as E-Bus Master)<br />

7.7.3 LocalCAN Bus Groups<br />

Slave<br />

QDIO<br />

Slave<br />

QDIO<br />

Number of slaves that may be attached to the RDIO:<br />

�-Table-12 on page 61<br />

(Additional<br />

Slaves)<br />

(Additional<br />

Slaves)<br />

LocalCAN bus groups are formed by joining <strong>MSC</strong> <strong>II</strong>s together at the Q-connectors.<br />

The modules within LocalCAN bus groups communicate over the internal<br />

LocalCAN bus.<br />

Observe the following when establishing LocalCAN bus groups:<br />

• The number of modules in a LocalCAN bus group is limited to 64 because<br />

CAN bus networks can only include a maximum of 64-network<br />

stations.<br />

�-"7.5.5.3-Number of Network Stations" on page 58<br />

• The switchable CAN bus termination resistor of the <strong>MSC</strong> <strong>II</strong> can be used<br />

as a termination resistor for the LocalCAN bus group.<br />

�-"10.15.1-CAN Bus Termination Resistor" on page 110<br />

• If a QEBUS-CAN is attached to the right, then the LocalCAN bus can be<br />

made available (using the QEBUS-CAN) for other CAN bus network stations<br />

that do not belong to the LocalCAN bus group.<br />

• Information about arranging DIN rail modules:<br />

�-"5.1.3-Arrangement on DIN Top-Hat Rails" on page 31<br />

E-Bus Group<br />

(<strong>MSC</strong> <strong>II</strong> as E-Bus Master)<br />

E-Bus Group<br />

(RDIO as E-Bus Master)<br />

LocalCAN Bus Groups<br />

© <strong>Moog</strong> GmbH <strong>User</strong> <strong>Manual</strong> M3000 ® and <strong>MSC</strong> <strong>II</strong> (CA65865-001; Version 1.1, 08/08) 66<br />

Slave<br />

QDIO<br />

Slave<br />

QDIO