6 Project Planning and Installation Power Supply<br />
U1<br />
+<br />
-<br />
I/O Group 1<br />
I/O1 I/O2<br />
2 37 2 20 38 3 21 39<br />
0V<br />
M1<br />
L2+ +24 V<br />
M1 0V<br />
L2+ +24 V<br />
I/O1 Signal<br />
M1 0V<br />
L2+ +24 V<br />
Sensor<br />
Actuator<br />
Signal<br />
I/O2<br />
IN5 I/O13<br />
1 6 24 42 32 14 32 50<br />
Figure 31: Correct Power Supply Connection of Sensors via a QDIO<br />
The attached sensors must be supplied with power from a permanently<br />
connected (unswitched) power supply that cannot be individually<br />
switched off, without switching off the module's power supply.<br />
Power must not, as shown in figure-32 on page 45, be supplied from<br />
switched power circuits!<br />
The sensors within an I/O group must always be supplied with power<br />
from the same power supply that supplies the relevant I/O group.<br />
They must not, as shown in figure-32 on page 45, be supplied from a<br />
separate power supply (due to the danger of reverse energization)!<br />
Outputs may be supplied with power from a switched power supply, for<br />
example with intermediate devices (emergency stop, manual operation,<br />
etc.).<br />
+24 V<br />
L1+<br />
0V<br />
M1<br />
+24 V<br />
L1+<br />
Sensor<br />
Signal<br />
IN5<br />
+24 V switched<br />
+24 V not switched<br />
Correct Power Supply<br />
Connection of Sensors via<br />
a QDIO<br />
© <strong>Moog</strong> GmbH <strong>User</strong> <strong>Manual</strong> M3000 ® and <strong>MSC</strong> <strong>II</strong> (CA65865-001; Version 1.1, 08/08) 44<br />
+24 V<br />
L3+<br />
0V<br />
QDIO 16/16-0,5<br />
I/O Group 2 I/O Group 3<br />
0V<br />
M1<br />
+24 V<br />
L3+<br />
Actuator<br />
Signal<br />
I/O13