6 Project Planning and Installation Power Supply<br />

6.2 Power Supply<br />

The internal electronics of M3000 ® modules is usually supplied with power<br />

via the power supply terminals of the connectors of the M3000 ® modules.<br />

Connecting the power supply for the internal electronics:<br />

�-"6.2.3-Connecting the Power Supply" on page 40<br />

Power supply terminals of the <strong>MSC</strong> <strong>II</strong>:<br />

�-"10.4.1-Terminal Assignment" on page 78<br />

Refer to the relevant documentation for the exact designations of the<br />

power supply terminals of the other M3000 ® modules.<br />

6.2.1 Power Supply Characteristics<br />

Output voltage<br />

Rated voltage: 24 V DC, operates at no-load<br />

SELV according to DIN EN 60950-1<br />

�-"6.2.1.1-Safety Extra-Low Voltage (SELV)"<br />

on page 39<br />

Run-up time (10–90 %): ≤ 0.2 sec.<br />

To ensure compatibility with other components, <strong>Moog</strong> recommends<br />

maintaining the power supply tolerance band specified in<br />

IEC 61131-2 (19.2 V to 30 V).<br />

Refer to the relevant documentation for the specified voltage<br />

ranges of the M3000 ® modules.<br />

Besides the specified voltage ranges, a total alternating voltage<br />

component with a peak value of 5 % of the rated voltage is also<br />

permitted.<br />

Output current<br />

If the output current of the power supply is greater than 12 A, the power<br />

cable to each M3000 ® module must be fused to ≤ 12 A or the current<br />

must be limited in another way.<br />

Maximum permissible duration of power interruptions<br />

Under full load (PS1 intensity): ≤ 1ms<br />

(duration of interruption during voltage drops and interruptions to the input<br />

voltage)<br />

During primary side voltage drops that are 1 ms or shorter in duration,<br />

the output voltage must not fall under 19.2 V when under full<br />

load. In addition, the interval between the primary side drops must<br />

not be shorter than 1 s.<br />

6.2.1.1 Safety Extra-Low Voltage (SELV)<br />

The safety extra-low voltage is a voltage that will not, under any operating<br />

conditions, exceed 25 V AC or 60 V DC peak or direct voltage as measured<br />

between conductors or between a conductor and ground. The circuit in which<br />

SELV is used must be separated from the mains power supply by a safety<br />

transformer or something of equal functionality. Always observe national regulations<br />

when choosing the rated insulation voltage.<br />

Power Supply for<br />

M3000 ® Modules<br />

Power Supply<br />

Characteristics of<br />

M3000 ® Modules<br />

Safety Extra-Low Voltage<br />

(SELV)<br />