5 Mechanical Installation DIN Rail Modules<br />

5.1.3 Arrangement on DIN Top-Hat Rails<br />

WARNING The vent holes of DIN rail modules facilitate convection<br />

cooling and must never be covered!<br />

Covered vent holes might result in overheating and fire.<br />

DIN rail modules must be arranged next to each other on a DIN top-hat rail<br />

TH 35-7.5 in accordance with DIN EN 60715.<br />

X1 X3<br />

X2<br />

WCAN<br />

L1+ TRM I/O1 I/O2 I/O3 I/O4 WCAN LCAN EBus Rx Tx Aux1 Aux2 Aux3 Aux4 OutEN<br />

1 2 3 4 5 6 7 8 9<br />

L1+ L1+ M1 M1 L2+ L2+ M2 M2 M2 X2<br />

X1<br />

X3<br />

OutEn I/O1 I/O2 I/O3 I/O4 M2 M2 M2 M2 X4<br />

WCAN WCAN<br />

Run<br />

X13<br />

X14<br />

X15 X16<br />

Stop !<br />

LAN RT-ETH1 RT-ETH2<br />

Reset<br />

X11 X12<br />

USB1 USB2 Link 100MB/s Link 100MB/s Link 100MB/s<br />

LK<br />

SIO F-Bus<br />

1 2 3 4 5 6 7 8 9 10<br />

X6<br />

X7<br />

X5 CLK+ CLK- A+ A- B+ B- Z+ Z- +5V DGND X8<br />

X9<br />

X10<br />

A1 B1 Z1 A2 B2 Z2 A3 B3 Z3 A4 B4 Z4 LED1 LED2 LED3 Error<br />

Figure 17: Arrangement of DIN Rail Modules on a Vertical Mounting Plate<br />

The DIN top-hat rail must be attached to a vertical, metal mounting plate and<br />

connected to the protective earth conductor.<br />

Additional information about the grounding concept for DIN rail modules:<br />

�-"6.1-Grounding Concept" on page 38<br />

Information about mounting/removing DIN rail modules:<br />

�-"5.1.4-Mounting and Removing" on page 33<br />

Maintain the minimum distances shown in figure-18 on page 32 to ensure:<br />

• Sufficient room for connecting the supply and signal cables<br />

• Sufficient room for mounting or removing the DIN rail modules<br />

• Convection cooling<br />

If operational reasons force the selection of other arrangements, the performance<br />

ratings of the DIN rail modules will decrease or forced cooling measures<br />

will be needed.<br />

Additional information about arranging DIN rail modules:<br />

�-"7.7.2-E-Bus Groups" on page 65<br />

X4<br />

X5 S1<br />

X8<br />

X6 S2<br />

X7<br />

1<br />

1 1 10<br />

SIO F-Bus<br />

X9 X10<br />

WCAN<br />

1 10<br />

Off On<br />

S3<br />

S4<br />

Arrangement of<br />

DIN Rail Modules on a<br />

Vertical Mounting Plate<br />

© <strong>Moog</strong> GmbH <strong>User</strong> <strong>Manual</strong> M3000 ® and <strong>MSC</strong> <strong>II</strong> (CA65865-001; Version 1.1, 08/08) 31