10 <strong>MSC</strong> <strong>II</strong> (<strong>Moog</strong> <strong>Servo</strong> Controller) Safety Functions<br />
As long as the 'Outputs Enabled' output is in the 1 state, the application program<br />
will control all outputs, the E-bus communication and the fieldbus communication.<br />
If the 'Outputs Enabled' output is switched to the 0 state (LED «OutEN» does<br />
not illuminate), all outputs will be disabled, the E-bus communication and the<br />
fieldbus communication will be stopped.<br />
In this case, although the internal states of the digital outputs are shown on<br />
the front panel status LEDs «I/O1»…«I/O4» of the <strong>MSC</strong> <strong>II</strong> control module,<br />
they are not connected through to the output.<br />
The digital output 'Outputs Enabled' will be switched to the 1 state only if the<br />
following conditions are fulfilled simultaneously:<br />
• An error-free application program has been loaded onto the <strong>MSC</strong> <strong>II</strong> control<br />
module and will be started once after every reset of the <strong>MSC</strong> <strong>II</strong> control<br />
module<br />
• A valid license key is inserted<br />
• The M_WATCHDOG function block is not used<br />
or the M_WATCHDOG function block is used in the application program,<br />
enabled and triggered cyclically within the set time<br />
If any one of these conditions is not fulfilled, the 'Outputs Enabled' output will<br />
be switched to the 0 state, thereby disabling all of the <strong>MSC</strong> <strong>II</strong> control module's<br />
other outputs. In addition, the E-bus and the fieldbus communication will be<br />
stopped.<br />
10.17.2.1 «OutEN» LED<br />
The front panel LED «OutEN», located of the <strong>MSC</strong> <strong>II</strong> control module, indicates<br />
the status of the 'Outputs Enabled' output. The LED «OutEN» illuminates<br />
when the 'Outputs Enabled' output is in the 1 state.<br />
10.17.3 Stopping the Application Program<br />
An application program (executed in the <strong>MSC</strong> <strong>II</strong> control module) can be<br />
stopped in the MACS development environment.<br />
After an application program stops, all analog and digital outputs will automatically<br />
be switched to a secure state. This secure value can be set for each<br />
output individually by modifying the 'Secure' channel parameter in the<br />
PLC Configuration.<br />
If the «OutEN» LED does not illuminate (when the 'Outputs Enabled'<br />
output is in the 0 state), this secure value will not be at the outputs because<br />
the outputs will be disabled.<br />
�-"10.17.2-'Outputs Enabled' Output (LED «OutEN»)" on page 111<br />
«OutEN» LED of the<br />
<strong>MSC</strong> <strong>II</strong> control module<br />
Stopping the<br />
Application Program<br />
© <strong>Moog</strong> GmbH <strong>User</strong> <strong>Manual</strong> M3000 ® and <strong>MSC</strong> <strong>II</strong> (CA65865-001; Version 1.1, 08/08) 112