10 <strong>MSC</strong> <strong>II</strong> (<strong>Moog</strong> <strong>Servo</strong> Controller) CAN Bus Interfaces<br />

10.15.1 CAN Bus Termination Resistor<br />

The LocalCAN interface of the <strong>MSC</strong> <strong>II</strong> is equipped with a switchable CAN bus<br />

termination resistor. The termination resistor can be switched on by a MACS<br />

function block in the application project.<br />

The «TRM» front panel status LED of the <strong>MSC</strong> <strong>II</strong> illuminates when the<br />

termination resistor of the LocalCAN interface is switched on.<br />

�-"10.4.2-LEDs" on page 81<br />

The switchable CAN bus termination resistor of the <strong>MSC</strong> <strong>II</strong> can be used as a<br />

termination resistor only on LocalCAN bus groups.<br />

�-"7.7.3-LocalCAN Bus Groups" on page 66<br />

In WideCAN bus groups, the switchable CAN bus termination resistor of the<br />

<strong>MSC</strong> <strong>II</strong> cannot be used as a termination resistor! Separate pluggable CAN<br />

termination resistors must be used for this.<br />

�-"7.7.4-WideCAN Bus Groups" on page 67<br />

D-sub connectors with CAN bus termination resistors are available from<br />

<strong>Moog</strong>.<br />

�-"11.7-CAN Bus Accessories" on page 120<br />

10.15.2 Setting the CANopen Node-ID<br />

The CANopen node-ID of the CAN bus interface of the <strong>MSC</strong> <strong>II</strong> control module<br />

can be set or modified in the following places:<br />

• In the application program<br />

• With the PLC Browser in the MACS development environment<br />

The CANopen node-ID is saved in the license key.<br />

�-"10.6.2-CANopen Node-ID and IP Address" on page 86<br />

10.15.3 Setting the CAN Bus Baud Rate<br />

The CAN bus baud rate is set in the application program.<br />

CAN Bus Termination<br />

Resistor of the <strong>MSC</strong> <strong>II</strong><br />

Setting/Modifying <strong>MSC</strong> <strong>II</strong><br />

control module's<br />

CANopen Node-ID<br />

© <strong>Moog</strong> GmbH <strong>User</strong> <strong>Manual</strong> M3000 ® and <strong>MSC</strong> <strong>II</strong> (CA65865-001; Version 1.1, 08/08) 110