10 <strong>MSC</strong> <strong>II</strong> (<strong>Moog</strong> <strong>Servo</strong> Controller) Power Supply<br />

10.8 Power Supply<br />

DANGER The 24 V power supply terminals of all M3000 ® modules are<br />

protected against reverse polarity.<br />

If the polarity of these power supply terminals is reversed, the<br />

modules will not work.<br />

WARNING M3000 ® modules must be protected from overvoltages<br />

and/or reverse energization from the sensor to the module!<br />

There is a danger of:<br />

• Permanent damage by overheating or fire<br />

• Malfunctions<br />

M3000 ® modules must have the correct voltage, polarity, and<br />

terminal assignments.<br />

Additional information about the power supply<br />

�-"10.2.2.3-Electrical Conditions and Requirements" on page 75<br />

�-"6.2-Power Supply" on page 39<br />

10.8.1 Behavior at Switching on and Switching off<br />

The following internal data resides in the flash EEPROM of the <strong>MSC</strong> <strong>II</strong> control<br />

module:<br />

• Boot projects<br />

• Error messages<br />

There is no battery buffered memory area. The <strong>MSC</strong> <strong>II</strong> control module is<br />

maintenance-free.<br />

WARNING If the most recent status in the online mode (MACS<br />

logged in) was 'Run' before the <strong>MSC</strong> <strong>II</strong> control module<br />

was switched off or reset, the boot project will always be<br />

started after the <strong>MSC</strong> <strong>II</strong> control module is switched back<br />

on or reset.<br />

This will occur regardless of which application program was<br />

previously running.<br />

In other words, the application program that will be started<br />

automatically after the <strong>MSC</strong> <strong>II</strong> control module is switched on<br />

or reset might be different from the application program that<br />

was executing immediately prior.<br />

Application programs can be saved and executed in the <strong>MSC</strong> <strong>II</strong> in the following<br />

manner:<br />

• As a boot project in the flash EEPROM<br />

• In RAM<br />

An application program saved as a boot project will be loaded into RAM<br />

whenever the <strong>MSC</strong> <strong>II</strong>'s power supply is switched on or when the <strong>MSC</strong> <strong>II</strong> is reset.<br />

Power Supply of the<br />

<strong>MSC</strong> <strong>II</strong> control module:<br />

Safety Instructions<br />

Contents of the<br />

Flash EEPROM<br />

Switching Back on or<br />

Resetting the <strong>MSC</strong> <strong>II</strong>:<br />

Safety Instructions<br />

© <strong>Moog</strong> GmbH <strong>User</strong> <strong>Manual</strong> M3000 ® and <strong>MSC</strong> <strong>II</strong> (CA65865-001; Version 1.1, 08/08) 89

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!