Two Heated Zone ResultsOne Stack Open Temperature StratificationTable 67. Scaled Temperatures <strong>for</strong> One Stack Open Model Experiment and Hypo<strong>the</strong>tical Full ScaleBuild<strong>in</strong>gModel Temp Build<strong>in</strong>g TempFirst Floor Column 1 Stack Open 1 Stack Open26 cm / 3 m 54.5 26.019 cm / 2.3 m 48.4 25.312 cm / 1.4 m 41.6 24.65 cm / 0.6 m 37.6 24.1First Floor Heated Zone 1 Stack Open 1 Stack Open27 cm / 3.2 m 63.1 26.921 cm / 2.5 m 59.6 26.615 cm / 1.8 m 56.6 26.29.5 cm / 1.1 m 54.8 26.03 cm / 0.4 m 44.7 24.9Ground Floor Column 1 Stack Open 1 Stack Open26 cm / 3 m 37.1 24.119 cm / 2.3 m 32.9 23.612 cm / 1.4 m 30.3 23.35 cm / 0.6 m 26.0 22.9Ground Floor Heated Zone 1 Stack Open 1 Stack Open27 cm / 3.2 m 33.4 23.721 cm / 2.5 m 31.2 23.415 cm / 1.8 m 31.7 23.59.5 cm / 1.1 m 41.6 24.63 cm / 0.4 m 40.7 24.5Atrium 1 Stack Open 1 Stack Open100 cm / 12 m 51.7 25.775 cm / 9 m 50.5 25.650 cm / 6 m 47.7 25.325 cm / 3 m 33.6 23.7203