ATV61 LON WORK - error
ATV61 LON WORK - error
ATV61 LON WORK - error
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
11. Network variables and configuration properties11. 7. Monitoring of analog inputsb Monitoring of analog input 1 (nvoAnalogIn1)This variable monitors the analog input 1 (%).NamenvoAnalogIn1SNVT referenceSNVT_lev_percentSNVT index 81Unit 0.005%Range -163 840% ... 163 830%Definition Value of the analog input 1This LonWorks network variable is linked to the drive parameter:Standardized image of analog input 1 (AI1r) (5232 = 16#1470).13 bit resolution (data range -8191 ... 8191).b Monitoring of analog input 2 (nvoAnalogIn2)This variable monitors the analog input 2 (%).NamenvoAnalogIn2SNVT referenceSNVT_lev_percentSNVT index 81Unit 0.005%Range -163 840% ... 163 830%Definition Value of the analog input 2This LonWorks network variable is linked to the drive parameter:Standardized image of analog input 2 (AI2r) (5233 = 16#1471).13 bit resolution (data range -8191 ... 8191).42