8. ConfigurationControl via LonWorks and switching of the setpoint at the terminals with application functionThe command comes from LonWorks. Input LI5 is used to switch the setpoint between LonWorks and the terminals. When switched to theterminals, the application functions (summing…) remain active.Configure the following parameters:Parameter Value CommentProfile Separate profile The commandand the setpoint can come from different channels.Setpoint 1 configuration Network card Setpoint 1 comes from LonWorks.Setpoint 1B configuration Analog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.Setpoint switching Input LI5 Input LI5 switches the reference (1 ↔ 1B).Command 1 configuration Network card Command 1 comes from LonWorks.Command switching Channel 1 Channel 1 is the command channel.Reference 1B is directly connected to the functions of the drive. If switching to the terminals is performed, the functions that affect thereference (summing, PID, etc) are active.Configuration via the graphic display terminal or the integrated display terminal:Menu Parameter Value[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [Separate] (SEP)[Ref.1 channel] (Fr1)[Com. card] (nEt)[Cmd channel 1] (cd1)[Com. card] (nEt)[Cmd switching] (CCS)[ch1 active] (Cd1)[1.7 - APPLICATION FUNCT.] (FUn-) [Ref.1B channel] (Fr1b)[Ref. AI1] (AI1)[REFERENCE SWITCH][Ref.1B switching] (rCb)[LI5] (LI5)18