Specifications9. <strong>BVM</strong>-<strong>40</strong> SpecificationsViewable Parameters• Maximum jar voltage.• Minimum jar voltage.• Selected jar voltage• Overall string voltage.Display• Backlit LCD, 4 x 20 characters.Power• 115VAC ±10% 60Hz, 200mA maximum.Fuses• One MDL 0.5A, located in the rear panel AC power block.Inputs• Up to <strong>40</strong> 12VDC jars.Outputs• LCD screen.Reading Accuracy• Cell voltage: ± 0.15% of reading ± 10mv• String voltage, 0 to 600V: 0.2% of reading, ±0.5VControl Switches• Power on/off: Main <strong>BVM</strong> rocker switch on rear panel.• Jar Select Two front panel momentary push button switches.Operating Environment• Temperature range: 5°C to <strong>40</strong>°C (41°F to 104°F)• Humidity range: 0% to 80% RH (non condensing) at 5°C to 31°C0% to 50% RH (non condensing) at 32°C to <strong>40</strong>°C• Indoor use only.• Installation category II• Pollution degree 2.Packaging• 7" width, 3.5" height, 14" depth.• Weight 7.3 lbs.11