Product InformationGD10P / GD10PEThe picture is slightly different <strong>in</strong> the case we would like to have the same response criteria for agas concentration of 25%LEL. For a trip response with<strong>in</strong> 2 seconds, the GD10PE at 10%LEL orthe GD10P-1s (fast) at 20%LEL is required. A response with<strong>in</strong> 1 second is possible with theGD10PE at 5%LEL only.2520Response at 25%LEL gasM<strong>in</strong>imumlevelsWarnTripGD10P-1s 15%LEL 20%LELGD10P-5s 10%LEL 20%LELGD10PE 3%LEL 4%LEL%LEL output1510GD10P-1sGD10P-5sGD10PE500 1 2 3 4 5secondsFor air <strong>in</strong>takes and for gas turb<strong>in</strong>e ventilation we may be concerned about gas concentration ofeven lower levels, here the GD10PE is the best option.Warn<strong>in</strong>g- and Trip-levelsWe recommend that a safety marg<strong>in</strong> of 100% (I.e. 2x) of the nom<strong>in</strong>al long term stabilitytolerance is used as the lowest level for a “warn<strong>in</strong>g” or “low alarm”. A warn<strong>in</strong>g should not <strong>in</strong>itiateany automatic shutdown action. For high alarm or trip, a m<strong>in</strong>imum level of 20% of full scale ofthe detector is recommended.It is also good practice to have a certa<strong>in</strong> distance between low and high alarm levels, and afactor of 2x has been the typical <strong>in</strong>dustry standard. With the trend of reduc<strong>in</strong>g alarm levels, thismarg<strong>in</strong> between warn<strong>in</strong>g and shutdown has been reduced <strong>in</strong> several projects.Choos<strong>in</strong>g the right GD10 for the taskGD10P- standard (“5 sec”)This detector should be the default choice as a general po<strong>in</strong>t detector. Depend<strong>in</strong>g on yourrequirements it is also suitable for air <strong>in</strong>takes and duct mount<strong>in</strong>g. Warn<strong>in</strong>g and trip levels can bedown to 10%LEL and 20% LEL respectively (2x marg<strong>in</strong>).GD10P – fast (“1 sec”)This detector is designed for fast response, and is very fast at trip levels (high alarm) of 20%LELand above. Please note that at a trip level of 20%, the m<strong>in</strong>imum warn<strong>in</strong>g level of 15% is quiteclose.GD10PEThis detector is 5 times as sensitive as standard po<strong>in</strong>t detectors, its scale cover<strong>in</strong>g 0 – 20%LEL.At gas concentrations above scale, it will ma<strong>in</strong>ta<strong>in</strong> an output of 20%LEL. GD10PE is designedfor fast detection of low gas concentrations. For detection of gas concentrations of less than20%LEL, i.e. when you need trip levels (high alarm) of 5 -15%LEL, the GD10PE is the bestsolution available.Page 2ProDetec Pty Ltd - Ph: +61 (0)2 9620 8700; <strong>in</strong>fo@prodetec.com.au

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!