Fault indication function block (Fb_Alarm)AlarmFault indication function block (Fb_Alarm)WAGO-I/O-PRO CAA Library ElementsCategory:Building AutomationName:Fb_AlarmType: Function Function block X ProgramLibrary name:Building_common.libApplicable to:All programmable fieldbus controllersInput Parameter: Data type: Comment:xAlarm BOOL TRUE at this input indicates an activealarmxQuit BOOL Handshake signal for the alarmxBlinkoption BOOL Selection of the flash optionDefault setting = FALSEFeedback Value: Data type: Comment:xAlarmsignal1 BOOL Acoustic alarm signal preferredxAlarmsignal2 BOOL Visual alarm signal preferredGraphical Display:Time Referenced Behavior:“xBlinkoption“ = FALSE“xBlinkoption“ = TRUExAlarmxQuitxAlarmsignal1xAlarmsignal2Subject to design changes WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 • D-32385 Minden Tel.: 05 71 / 8 87-0 E-Mail: info@wago.comCopyright © 2009 Hansastr. 27 • D-32423 Minden Fax.: 05 71 / 8 87-169 Web:http://www.wago.com6

Fault indication function block (Fb_Alarm)Function Description:If the signal at the “xAlarm“ input changes to 1, both outputs “xAlarmsignal1“ and“xAlarmsignal2“ will be activated. Once the alarm is acknowledged by a signal atinput “xQuit“, output “xAlarmsignal1“ is reset. Should another alarm be pending,output “xAlarmsignal2“ can adopt two different states: switched on or flashing (1Hz). Depending on the selected option “xBlinkoption“ , the flashing status of analarm is: pending and acknowledged pending and not acknowledgedSubject to design changes WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 • D-32385 Minden Tel.: 05 71 / 8 87-0 E-Mail: info@wago.comCopyright © 2009 Hansastr. 27 • D-32423 Minden Fax.: 05 71 / 8 87-169 Web:http://www.wago.com7

Fault indication function block (Fb_Alarm)<strong>Function</strong> Description:If the signal at the “xAlarm“ input changes to 1, both outputs “xAlarmsignal1“ and“xAlarmsignal2“ will be activated. Once the alarm is acknowledged by a signal atinput “xQuit“, output “xAlarmsignal1“ is reset. Should another alarm be pending,output “xAlarmsignal2“ can adopt two different states: switched on or flashing (1Hz). Depending on the selected option “xBlinkoption“ , the flashing status of analarm is: pending and acknowledged pending and not acknowledgedSubject to design changes WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 • D-32385 Minden Tel.: 05 71 / 8 87-0 E-Mail: info@wago.comCopyright © 2009 Hansastr. 27 • D-32423 Minden Fax.: 05 71 / 8 87-169 Web:http://www.wago.com7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!