Dimmer Single Switch (FbDimmerSingleSwitch)The minimum and the maximum light level is entered as a default value by means ofthe parameters “bMinDimmValue“ and “bMaxDimmValue“.Parameter “uiT_SpeedIn10telSec“ is the dimming time during which the light signalchanges from “bMinDimmValue“ to “bMaxDimmValue“.If <strong>for</strong> the time “uiT_SpeedIn10telSec“ a value outside of the value range (30 – 1000[0.1s]) is entered, then the top or the bottom limit value is set.Parameter “bModeOnReset“ determines the function block behavior following areset at the coupler. The following settings are possible <strong>for</strong> this parameter:0 = Switching OFF following a reset1 = Switching ON following a reset3 = No change following a reset (the initial value be<strong>for</strong>e reset is restored)Note:This function block uses some residual variables having a VAR_RETAINdeclaration.Subject to design changes WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 • D-32385 Minden Tel.: 05 71 / 8 87-0 E-Mail: info@wago.comCopyright © 2009 Hansastr. 27 • D-32423 Minden Fax.: 05 71 / 8 87-169 Web:http://www.wago.com26