Rotary and Static UPS Technologies - Critical Facilities Round Table
Rotary and Static UPS Technologies - Critical Facilities Round Table
Rotary and Static UPS Technologies - Critical Facilities Round Table
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Input of Br<strong>and</strong> “X” Double Conversion <strong>UPS</strong>at Full Linear LoadVolts400Powerware InputAmps20003001500200100010050000-100-500-200-1000CVCI-300-1500AV-400-200017:21:22,000 17:21:22,005 17:21:22,010 17:21:22,015 17:21:22,020CHA Volts CHB Volts CHC Volts CHA Amps CHB Amps CHC AmpsBIBVAITimed event at 12.10.2000 17:21:22,000Sync channel =CHA (4 WIRE 3 PROBE)Unit A B C D ABCV 268.1 269.8 269.0 268.8 269.0I 645.6 649.4 647.4 0.0 1942.5kW 144.0 146.4 145.1 0.0 435.5kVA 173.1 175.2 174.2 0.0 522.5kVAR 96.0 96.2 96.3 0.0 288.6PF 0.832 0.836 0.833 0.000 0.834VTHD 5.87 5.63 5.85 5.95ITHD 29.76 29.90 30.17 0.00V H3 2.9 2.8 2.4 3.2I H3 0.5 0.0 0.3 0.0KFact 6.3 6.4 6.5 0.0Dem<strong>and</strong> 131.8 134.4 133.1 0.0 399.2 (kW)Energy 60.1 62.7 62.0 0.0 184.7 (kWh)ICF 4.3 1.9 1.6 0.0HZ 60.0Vunbal 0.3<strong>Critical</strong> <strong>Facilities</strong> <strong>Round</strong> <strong>Table</strong>8/27/2004Power Conversion Technology Options