Proline Promass 83E/F/O Operation Manual - FMC Technologies
Proline Promass 83E/F/O Operation Manual - FMC Technologies
Proline Promass 83E/F/O Operation Manual - FMC Technologies
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Wiring <strong>Proline</strong> <strong>Promass</strong> 83Fig. 23: Connecting the transmitter (stainless steel field housing); cable cross-section: max. 2.5 mm a Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DCTerminal No. 1: L1 for AC, L+ for DCTerminal No. 2: N for AC, L- for DCb Signal cable: Terminals Nos. 20–27 ä 29c Ground terminal for protective groundd Ground terminal for signal cable shielde Service adapter for connecting service interface FXA193 (FieldCheck, FieldCare)f Cover of the connection compartmentFig. 24: Connecting the transmitter (wall-mount housing); cable cross-section: max. 2.5 mm a Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DCTerminalNo. 1: L1 for AC, L+ for DCTerminalNo. 2: N for AC, L- for DCb Signal cable: Terminals Nos. 20–27 ä 29c Ground terminal for protective groundd Ground terminal for signal cable shielde Service adapter for connecting service interface FXA193 (FieldCheck, FieldCare)f Cover of the connection compartmentPage 28 • MN0M022Issue/Rev. 0.2 (12/12)