kn series gas boiler installation & operating ... - Agencespl.com

kn series gas boiler installation & operating ... - Agencespl.com kn series gas boiler installation & operating ... - Agencespl.com

agencespl.com
from agencespl.com More from this publisher
12.07.2015 Views

Page 4KN INSTALLATION AND OPERATION INSTRUCTIONSBuildings will require the installation of a fresh air ductor other means of providing make-up air if the intakeair option isn't used. Any building utilizing other gasburning appliances, a fireplace, wood stove or any typeof exhaust fan must be checked for adequatecombustion air when all of these devices are inoperation at one time. Sizing of an outside air duct mustbe done to meet the requirements of all such devices.WARNING: Never operate the KN-10 in anenvironment subjected to a negative pressureunless it is Direct Vented. Failure to comply withthis warning can result in excessive levels ofcarbon monoxide causing severe personalinjury or death!All Air From Inside The BuildingIf the boiler is to be located in a confined space theminimum clearances listed in Table 1 must bemaintained between it and any combustible construction.When installed in a confined space without the intakeair option two permanent openings communicating withan additional room(s) are required. The combinedvolume of these spaces must have sufficient volume tomeet the criteria for an unconfined space. The total airrequirements of all gas utilization equipment, fireplaces,wood stoves or any type of exhaust fan must beconsidered when making this determination. Eachopening must have a minimum free area of 1 in 2 /1000Btu/hr, 2200 mm 2 /kW based on the total input rating ofALL gas utilization equipment in the confined area. Eachopening must be no less than 100 in 2 , 64,516 mm 2 insize. The upper opening must be within 12 in, 300 mmof, but not less than 3 in, 80 mm from, the top of theenclosure. The bottom opening must be within 12 in,300 mm of, but not less than 3 in, 80 mm from, thebottom of the enclosure.All Air From Outside The BuildingWhen installed in a confined space without the intakeair option two permanent openings communicatingdirectly with, or by ducts to, the outdoors or spaces thatfreely communicate with the outdoors must be present.The upper opening must be within 12 in, 300 mm of,but not less than 3 in, 80 mm from, the top of theenclosure. The bottom opening must be within 12 in,300 mm of, but not less than 3 in, 80 mm from, thebottom of the enclosure.Where directly communicating with the outdoors orcommunicating with the outdoors through vertical ducts,each opening shall have a minimum free area of 1 in 2 /4000 Btu/hr, 550 mm 2 /kW of the total input rating of allof the equipment in the enclosure.When ducts are used, they must have the same crosssectionalarea as the free area of the opening to whichthey connect.Table 2 - Make-up Air Duct SizingRequired Cross Sectional Duct AreaInput 1/4 in, 6.4 mm Metal Wooden(MBH) Wire Screen Louvers Louversin 2 cm 2 in 2 cm 2 in 2 cm 2600 150 967 200 1292 600 38691000 250 1612 334 2154 1000 64482000 500 3224 668 4308 2000 12,896When calculating the free area necessary to meet themake-up air requirements of the enclosure,consideration must be given to the blockage effects oflouvers, grills and screens.Screens must have a minimum mesh size of 1/4 in,6.4 mm. If the free area through a louver or grill is notknown ducts should be sized per Table 2 above.Direct Intake Air Option - GeneralThis configuration provides combustion air directly to theboiler’s air intake using a dedicated pipe when using thedirect vent option. Combustion air can be drawn inhorizontally through an outside wall or vertically throughthe roof, see Figures 1, 2, 3 & 4. It must be sized perTable 3.WARNING: Each boiler must have it’s own intakeair system. Common intake air systems are notto be used! Improper installation can result inexcessive levels of carbon monoxide which cancause severe personal injury or death!Single wall galvanized smoke pipe, single wall aluminumpipe, flexible aluminum pipe, PVC or CPVC pipe can beused for the intake air pipe.Table 3 - Intake Air Pipe SizingModelPipe DiameterSize in 2 mm 2600 5 1271000 6 1522000 9 229All joints in metal intake air systems must be securedusing corrosion resistant fasteners and sealed using asuitable Silicone caulk. If PVC or CPVC is used, thejoints must be cleaned with a suitable solvent andconnected using a solvent based PVC cement. Theintake air system MUST be supported by the buildingstructure not the boiler.Where communicating with the outdoors through horizontalducts, each opening shall have a minimum freearea of 1 in 2 /2000 Btu/hr, 1100 mm 2 /kW of the totalinput rating of all of the equipment in the enclosure.

KN INSTALLATION AND OPERATION INSTRUCTIONSPage 5Direct Intake Air Option - VerticalThe maximum equivalent length for the vertical intakeair pipe is 80 ft, 19.7 m. Each 90° mitered elbow andthe intake air cap are equal to 10 ft, 3.3 m of straightpipe. If 90° long sweep elbows are installed use themanufacturers recommended equivalent length.A listed, nonrestrictive intake air cap must be used. Theintake air cap must terminate as shown in Figure 3. Thepenetration point in the roof must be properly flashedand sealed. Approved caps are listed in Table 4.Direct Intake Air Option - HorizontalThe maximum equivalent length for the horizontal intakeair pipe is 80 ft, 19.7 m. Each 90° mitered elbow andthe intake air terminal are equal to 10 ft, 3.3 m ofstraight pipe. If 90° long sweep elbows are installed usethe manufacturers recommended equivalent length.Horizontal runs that exceed 5 ft, 1.5 m must besupported at 3 ft, 0.98 m intervals with overheadhangers. The intake air terminal must terminate asshown in Figures 1, 2 or 4. Approved terminals are listedin Table 5.Table 4 - Vertical Intake & Vent System ComponentsCompany Description Part Number Dia., inFlex-L 5Flex-L 6Flex-L 9Heat Fab Rain Cap 5500CI 5Heat Fab Rain Cap 5600CI 6Heat Fab Rain Cap 51000CI 9Pro Tech Rain Cap FSRC5 5Pro Tech Rain Cap FSRC6 6Pro Tech Rain Cap FSRC10 9Z Flex 5Z Flex 6Z Flex 9GENERAL VENTING GUIDELINESWARNING: The vent installation must be inaccordance with Part 7, Venting of Equipment,of the National Fuel Gas Code, ANSI Z223.1/NFPA54-latest revision or applicable provisions ofthe local building codes. Canadian installationsmust comply with CSA B149.1 or .2 InstallationCode. Improper venting can result in excessivelevels of carbon monoxide which can result insevere personal injury or death!All vent systems must be fully supported by the buildingstructure and not by the boiler. Appropriate thimbles andfire-stops must be used where required.Table 5 - Horizontal Intake & Vent SystemComponentsCompany Description Part Number Dia., inFlex-L Vent Adapter 5Flex-L Vent Adapter 6Flex-L Vent Adapter 9Termination TTermination TTermination TTermination ELTermination ELTermination ELHeat Fab Vent Adapter 9501KN10 5Heat Fab Vent Adapter 9601KN10 6Heat Fab Vent Adapter 91001KN10 9Termination T 9590TEE 5Termination T 9690TEE 6Termination T 90990TEE 9Termination EL 7514TERM 5Termination EL 9614TERM 6Termination EL 90914TERM 9Pro Tech Vent Adapter 5Pro Tech Vent Adapter FSA-HFAG 6Pro Tech Vent Adapter 9Termination T 300313 5Termination T 300314 6Termination T 9Termination EL 5Termination EL 6Termination EL 9Z Flex Vent Adapter 5Vent Adapter 6Vent Adapter 9Termination T 02SVSTTX05 5Termination T 6Termination T 9Termination EL 5Termination EL 6Termination EL 9WARNING: Each boiler must have it’s own ventsystem. Common positive pressure vent systemsare not to be used! Improper installation canresult in excessive levels of carbon monoxidewhich can cause severe personal injury or death!Note: A single acting barometric damper must beinstalled in the vent connector if a vertical ventsystem produces a draft in excess of 0.08 in,2.03 mm W.C at the flue outlet.Note: One of the vent system adapters listed in Table5 must be attached to the flue outlet of the boilerbefore the vent system is connected.

Page 4KN INSTALLATION AND OPERATION INSTRUCTIONSBuildings will require the <strong>installation</strong> of a fresh air ductor other means of providing make-up air if the intakeair option isn't used. Any building utilizing other <strong>gas</strong>burning appliances, a fireplace, wood stove or any typeof exhaust fan must be checked for adequate<strong>com</strong>bustion air when all of these devices are inoperation at one time. Sizing of an outside air duct mustbe done to meet the requirements of all such devices.WARNING: Never operate the KN-10 in anenvironment subjected to a negative pressureunless it is Direct Vented. Failure to <strong>com</strong>ply withthis warning can result in excessive levels ofcarbon monoxide causing severe personalinjury or death!All Air From Inside The BuildingIf the <strong>boiler</strong> is to be located in a confined space theminimum clearances listed in Table 1 must bemaintained between it and any <strong>com</strong>bustible construction.When installed in a confined space without the intakeair option two permanent openings <strong>com</strong>municating withan additional room(s) are required. The <strong>com</strong>binedvolume of these spaces must have sufficient volume tomeet the criteria for an unconfined space. The total airrequirements of all <strong>gas</strong> utilization equipment, fireplaces,wood stoves or any type of exhaust fan must beconsidered when making this determination. Eachopening must have a minimum free area of 1 in 2 /1000Btu/hr, 2200 mm 2 /kW based on the total input rating ofALL <strong>gas</strong> utilization equipment in the confined area. Eachopening must be no less than 100 in 2 , 64,516 mm 2 insize. The upper opening must be within 12 in, 300 mmof, but not less than 3 in, 80 mm from, the top of theenclosure. The bottom opening must be within 12 in,300 mm of, but not less than 3 in, 80 mm from, thebottom of the enclosure.All Air From Outside The BuildingWhen installed in a confined space without the intakeair option two permanent openings <strong>com</strong>municatingdirectly with, or by ducts to, the outdoors or spaces thatfreely <strong>com</strong>municate with the outdoors must be present.The upper opening must be within 12 in, 300 mm of,but not less than 3 in, 80 mm from, the top of theenclosure. The bottom opening must be within 12 in,300 mm of, but not less than 3 in, 80 mm from, thebottom of the enclosure.Where directly <strong>com</strong>municating with the outdoors or<strong>com</strong>municating with the outdoors through vertical ducts,each opening shall have a minimum free area of 1 in 2 /4000 Btu/hr, 550 mm 2 /kW of the total input rating of allof the equipment in the enclosure.When ducts are used, they must have the same crosssectionalarea as the free area of the opening to whichthey connect.Table 2 - Make-up Air Duct SizingRequired Cross Sectional Duct AreaInput 1/4 in, 6.4 mm Metal Wooden(MBH) Wire Screen Louvers Louversin 2 cm 2 in 2 cm 2 in 2 cm 2600 150 967 200 1292 600 38691000 250 1612 334 2154 1000 64482000 500 3224 668 4308 2000 12,896When calculating the free area necessary to meet themake-up air requirements of the enclosure,consideration must be given to the blockage effects oflouvers, grills and screens.Screens must have a minimum mesh size of 1/4 in,6.4 mm. If the free area through a louver or grill is not<strong>kn</strong>own ducts should be sized per Table 2 above.Direct Intake Air Option - GeneralThis configuration provides <strong>com</strong>bustion air directly to the<strong>boiler</strong>’s air intake using a dedicated pipe when using thedirect vent option. Combustion air can be drawn inhorizontally through an outside wall or vertically throughthe roof, see Figures 1, 2, 3 & 4. It must be sized perTable 3.WARNING: Each <strong>boiler</strong> must have it’s own intakeair system. Common intake air systems are notto be used! Improper <strong>installation</strong> can result inexcessive levels of carbon monoxide which cancause severe personal injury or death!Single wall galvanized smoke pipe, single wall aluminumpipe, flexible aluminum pipe, PVC or CPVC pipe can beused for the intake air pipe.Table 3 - Intake Air Pipe SizingModelPipe DiameterSize in 2 mm 2600 5 1271000 6 1522000 9 229All joints in metal intake air systems must be securedusing corrosion resistant fasteners and sealed using asuitable Silicone caulk. If PVC or CPVC is used, thejoints must be cleaned with a suitable solvent andconnected using a solvent based PVC cement. Theintake air system MUST be supported by the buildingstructure not the <strong>boiler</strong>.Where <strong>com</strong>municating with the outdoors through horizontalducts, each opening shall have a minimum freearea of 1 in 2 /2000 Btu/hr, 1100 mm 2 /kW of the totalinput rating of all of the equipment in the enclosure.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!