16 Fault FindingF1 FAULT DISPLAYEDFAULT: THE BURNER DOES NOT LIGHT AT ALL, BUT THERE IS AN IGNITION SPARK.Are the gas taps on?YESIs there 24Vdc at the gas control valve?for testing see component testing data.YESTest the gas control valve.Check resistance of safety valve coil.NONOTurn on the gas taps.Check the wiring.If the problem persists, change thecontrol board (PCB).FAULT: THE ROOM TEMPERATURE IS INADEQUATE AND RADIATORS ARE LUKE-WARM.Is the room thermostat and or radiatorset high enough and calling for duty?NOYESIs the heating temperature on the boilerset high enough?YESTurn up settingsIs the heating power adequate?- Check set point P3. (Refer to Commissioning)- Check dip switch setting. (Refer to Commissioning)- Check the adjustment of the by-pass internal andexternal (If fitted). - F24E Only Check the 3-way valveis not passing into the domestic hot water heat exchanger.4000124050-238

16 Fault FindingF24E ONLYFAULT: THE WATER AT THE TAPS IS LUKE-WARM.Is the temperature higher if you reducethe flow through the taps?NOCheck the 3-way valve is not passinginto the radiators. (The radiators shouldstay cold in Summer setting)YESCheck that the cold water inlet restrictoris fitted.Check the rate of flow.Check burner pressure is correct.11875FAULT: THE FAN DOES NOT START.Is there is 230V acat fan during demand?NOCheck continuity of fan harness.YESFaulty fan, replace.YESFaulty PCB, replace.11876FAULT: THE FAN RUNS BUT THERE ARE NO SPARKS.• CHECK CONTINUITY OF IGNITION (ELECTRODES AND LEADS)• CHECK POWER SUPPLY FROM PCB TO IGNITION UNITCONNECTIONS TO THE AIR PRESSURE SWITCHPrP1P232 1HLAir flow switch take-off.Electrical contacts.1187739 4000124050-2

16 Fault FindingF24E ONLYFAULT: THE WATER AT THE TAPS IS LUKE-WARM.Is the temperature higher if you reducethe flow through the taps?NOCheck the 3-way valve is not passinginto the radiators. (The radiators shouldstay cold in Summer setting)YESCheck that the cold water inlet restrictoris fitted.Check the rate of flow.Check burner pressure is correct.11875FAULT: THE FAN DOES NOT START.Is there is 230V acat fan during demand?NOCheck continuity of fan harness.YESFaulty fan, replace.YESFaulty PCB, replace.11876FAULT: THE FAN RUNS BUT THERE ARE NO SPARKS.• CHECK CONTINUITY OF IGNITION (ELECTRODES AND LEADS)• CHECK POWER SUPPLY FROM PCB TO IGNITION UNITCONNECTIONS TO THE AIR PRESSURE SWITCHPrP1P232 1HLAir flow switch take-off.Electrical contacts.1187739 4000124050-2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!