15 Routine Cleaning and Inspection9811Diagram 15.515.11 Heat exchanger, refer to diagram 15.9• Remove air pressure switch sensing tube from the side ofthe flue hood.• Unscrew and remove the two retaining screws from front ofeach side panel.• Unhook each panel from the front retaining tabs and easeoutwards.• Remove the flue hood. When refitting ensure the rear of theflue hood locates in the tabs.• Use a soft brush or vacuum clean the heat exchanger.DO NOT USE ANY TOOL LIKELY TO DAMAGE PAINTEDFINISH OF HEAT EXCHANGER.3.5mm97529741EARTHLEADFAN RETAININGSCREWS3.5mmIGNITIONGAP3.5 mm9816FLAMESENSING GAPDiagram 15.6POWERSUPPLYLEADSDiagram 15.89812BURNERRETAININGSCREWSBURNERGUIDE9817 98189742AIR PRESSURESWITCHSENSING TUBEFLUE HOOD97509818Diagram 15.7HEAT EXCHANGERDiagram 15.94000124050-232
15 Routine Cleaning and Inspection15.12 (F24E Only) Domestic water inlet filter,refer to diagram 15.10If the water flow rate through the appliance has reduced it maybe necessary to clean or replace the domestic water inlet filter.DOMESTIC WATERINLET FILTERHOUSINGCLIP9822• Close isolating valve (b) on cold water inlet.• Pull out slotted clip securing the filter in its housing, remove thefilter to clean or renew if necessary.Push the filter fully into its housing and replace the securing clip.• Open isolating valve, (b) diagram 15.2, on cold water inlet andtest the Domestic Hot Water circuit for soundness.15.13 Central Heating Filter, refer to diagram15.11Remove the filter retaining clip and filter clean or renew ifnecessary.Push the filter fully into its housing, ensuring the correctorientation. The flat and hole in the filter as shown. Secure withretaining clip.F24E onlyFILTERDiagram 15.1015.14 Sealed chamber cover seal check• Check the condition of the seal, replace as required.• To replace remove the old seal, thoroughly clean the casingsurfaces. Fit new seal, it is supplied to the correct length, seediagram 18.25.1193415.15 Combustion chamber insulation• Check the condition of the combustion chamber insulation.If renewing, refer to Section 18.14.15.16 Flue system• Check externally to make sure that flue is not blocked• Inspect flue system to make sure that all fittings are secure.15.17 Reassembly of parts removed forservicingRETAININGCLIPFILTERFLATAll parts are replaced in reverse order to removal.11935F24E shownDiagram 15.1133 4000124050-2
- Page 1 and 2: To be left with the user4000124050-
- Page 3 and 4: ContentsCONTENTS DESCRIPTION SECTIO
- Page 5 and 6: Draining and FillingCaution: The bo
- Page 7: User Controls and LightingCentral h
- Page 10 and 11: Programmer Instructions for UseEven
- Page 12 and 13: 1 Technical DataThe F24E and F18E S
- Page 14 and 15: 3 Heating System Design3.1 Bypass
- Page 16 and 17: 5 Boiler Schematic F24E1 - Fan.2 -
- Page 18 and 19: 7 Fixing JigThe fixing jig is made
- Page 20 and 21: 9 Boiler Installation9.1 Sheet meta
- Page 22 and 23: 10 Horizontal Telescopic Top Flue I
- Page 24 and 25: 18410a Horizontal Top Flue Installa
- Page 26 and 27: 11.3 Mains Voltage External Control
- Page 28 and 29: 112 Commissioning5. • Bleed each
- Page 30 and 31: 15 Routine Cleaning and InspectionR
- Page 34 and 35: 16 Fault FindingBefore trying to op
- Page 36 and 37: 16 Fault FindingFAULT: NO HEATINGAr
- Page 38 and 39: 16 Fault FindingF1 FAULT DISPLAYEDF
- Page 40 and 41: 17 Wiring Diagram F24EgorFANg/yOVER
- Page 42 and 43: 18 Replacement of PartsTo Drain the
- Page 44 and 45: 18 Replacement of Parts18.9 Burner
- Page 46 and 47: 18 Replacement of Parts230V CONTROL
- Page 48 and 49: 18.25 System water pressure sensor,
- Page 50 and 51: 18 Replacement of Parts18.32 (F24E
- Page 52: 19 Spare partsWhen ordering spare p
15 Routine Cleaning and Inspection15.12 (F24E Only) Domestic water inlet filter,refer to diagram 15.10If the water flow rate through the appliance has reduced it maybe necessary to clean or replace the domestic water inlet filter.DOMESTIC WATERINLET FILTERHOUSINGCLIP9822• Close isolating valve (b) on cold water inlet.• Pull out slotted clip securing the filter in its housing, remove thefilter to clean or renew if necessary.Push the filter fully into its housing and replace the securing clip.• Open isolating valve, (b) diagram 15.2, on cold water inlet andtest the Domestic Hot Water circuit for soundness.15.13 Central Heating Filter, refer to diagram15.11Remove the filter retaining clip and filter clean or renew ifnecessary.Push the filter fully into its housing, ensuring the correctorientation. The flat and hole in the filter as shown. Secure withretaining clip.F24E onlyFILTERDiagram 15.1015.14 Sealed chamber cover seal check• Check the condition of the seal, replace as required.• To replace remove the old seal, thoroughly clean the casingsurfaces. Fit new seal, it is supplied to the correct length, seediagram 18.25.1193415.15 Combustion chamber insulation• Check the condition of the combustion chamber insulation.If renewing, refer to Section 18.14.15.16 Flue system• Check externally to make sure that flue is not blocked• Inspect flue system to make sure that all fittings are secure.15.17 Reassembly of parts removed forservicingRETAININGCLIPFILTERFLATAll parts are replaced in reverse order to removal.11935F24E shownDiagram 15.1133 4000124050-2