4 Domestic Hot Water System Design. F24E OnlyGeneral - All domestic hot water circuits, connections, fittingsmust be in accordance with the relevant standards and watersupply regulations.For GB: Guidance G17 to G24 and recommendation R17 toR24 of the Water Regulation Guide.For IE: The current edition of I.S.813 "Domestic Gas<strong>Installation</strong>s".• Copper tubing or plastic Hep 20 may be used for the domestichot water system. Unnecessary pressure losses should beavoided.• Provision shall be made for a drain valve at the lowest pointsof the system.• The flow restrictor, supplied in the document envelope, mustbe fitted as diagram 7.1, limiting the flow through the boiler toa maximum of 10 litres/min.• The boiler will operate with a minimum supply pressure of 0.5bar, at a reduced flow rate.Best operating performance will be obtained from a supplypressure of 1 bar or greater.4.1 Hard Water AreasIn areas where the water is 'hard', more than 200mg/litre, it isrecommended that a proprietary scale reducer is fitted in thecold water supply to the boiler.15 4000124050-2