General DataTable 5 - Evaporator hydraulic module205 206 207 208 209 210 211High head pressure optionNumber of pump sets 1Motor (1) (2) (kW) 4.0 4.0 5.5 5.5 5.5 7.5 7.5Rated Amps (1) (2) (A) 7.5 7.5 11.1 11.1 11.1 14.7 14.7Motor RPM (rpm) 2900Low head pressure optionNumber of pump sets 1Motor (1) (2) (kW) 2.2 2.2 4.0 4.0 4.0 5.5 5.5Rated Amps (1) (2) (A) 4.4 4.4 7.5 7.5 7.5 11.1 11.1Motor RPM (rpm) 2900Expansion tank volume (l) 25User volume expansion capacity (3) (l) 12000Water strainer diameter 3" 3" 4" 4" 4" 4" 4"Piping(1) Per motor(2) Dual pump option(3) Hydrostatic pressure 3 bar at 45°C with -12°C miniSteelTable 6 - Condenser hydraulic module205 206 207 208 209 210 211High head pressure optionNumber of pump sets2 (in parallel)Motor (1) (2) (kW) 3 3 4 4 4 4 4Rated Amps (1) (2) (A) 6.1 6.1 7.7 7.7 7.7 7.7 7.7Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 2900Low head pressure optionNumber of pump sets2 (in parallel)Motor (1) (2) (kW) 2.2 2.2 3 3 3 3 3Rated Amps (1) (2) (A) 4.2 4.2 6.1 6.1 6.1 6.1 6.1Motor RPM (rpm) 2900Water strainer diameter - low head 3" 3" 4" 4" 4" 4" 4"Water strainer diameter - high head 4" 4" 4" 4" 4" 4" 4"Piping(1) Per motor(2) Dual pump option(3) Hydrostatic pressure 3 bar at 45°C with -12°C miniSteel8CG-SVX06A-E4