<strong>Installation</strong>Operating rangeCAUTION: Maximum operating timefor low condensing water outlet is1 minute. The compressor shallbecome noisy.The envelope represents theoperating range in which the unitwill work without control limitation.To keep the unit operating in thisenvelope, be careful to adjustsetpoints inside with a clearanceequal to half the dead band. Checkalso compressor suction superheatfor being close to 5 or 6°C for lowchilled leaving water temperature tominimize compressor dischargetemperature. For very high leavingcondensing water temperatureabove 55°C, the refrigerant chargecan be minimized by 20%.Figure 17 - CGWN operating limitsCLWT : Condenser Leaving Water TemperatureELWT : Evaporator Leaving Water TemperatureCG-SVX06A-E429