<strong>Installation</strong>Winter freeze protectionDuring negative ambient airtemperature chilled water pipingmust be fully insulated. Ensure thatall safeties are taken to preventfrost damage during negativeambient air temperature. Thefollowing systems can be used:• Electrical heater mounted on allwater piping exposed tonegative temperatures.• Start chilled water pump duringnegative ambient airtemperature.• Add ethylene glycol in the chilledwater.• Drain water-circuit, however beaware of corrosion process whendrained.CAUTION: There is a risk of freezeupof the evaporator circuit due tointernal refrigerant migration if thecondenser circuit is maintained at alow temperature (below 0°C) for along period during the cold season.If necessary, provide isolationvalves on the condenser watercircuit (CGWN). CCUN is protectedagainst refrigeration migration by aliquid solenoid valve.Figure 13 - Freezing point versus ethylene glycol percentage0-1 0Brine temperature (°C)-2 0-3 0321-4 0-5 00 1 0 2 0 3 0 4 0 5 0 6 01. Liquid2. Freezing without burst effect3. Freezing with burst effect% Ethylene glycolCG-SVX06A-E425