<strong>Installation</strong>The minimum required subcoolingat the remote condenser level wheninstalled below is defined in thefollowing table.Example : If the remote condenseris 10m below the CCUN and thecondensing temperature is 50°C, therefrigerant subcooling leaving theremote condenser shall not bebelow 4°C. To increase the amountof subcooling, more refrigerantcharge is required.Table 10 - Maximum elevation (H) of CCUN above RTCASubcooling°CCondensing dew temperature °C20°C 35°C 50°C 65°C4°C 4 m 6 m 8 m 10 m6°C 8 m 12 m 16 m 20 m8°C 12 m 17 m 23 m 30 m10°C 16 m 23 m 30 m 40 m12°C 20 m 28 m 38 m 49 mTable 11 - Recommended discharge line diameters for vertical risersUnit sizeLeaving chilled water temperature (°C)-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14CCUN 205 7/8" 1"1/8 1"3/8CCUN 206 7/8" 1"1/8 1"3/8 1"5/8CCUN 207 1"1/8 1"3/8 1"5/8CCUN 208 1"1/8 1"3/8 1"5/8CCUN 209 1"1/8 1"3/8 1"5/8CCUN 210 1"1/8 1"3/8 1"5/8CCUN 211 1"1/8 1"3/8 1"5/8Table 12 - Recommended liquid line diameters (either horizontal or vertical)Unit sizeLeaving chilled water temperature (°C)-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14CCUN 205 7/8" 1"1/8CCUN 206 7/8" 1"1/8CCUN 207 7/8" 1"1/8 1"3/8CCUN 208 7/8" 1"1/8 1"3/8CCUN 209 7/8" 1"1/8 1"3/8CCUN 210 1"1/8 1"3/8 1"5/8CCUN 211 1"1/8 1"3/8 1"5/822CG-SVX06A-E4