<strong>HIMax</strong>7 Input Modules7.5.4 Surges on Digital InputsNOTICEIf shielded cables are used for digital inputs, no additional precautionary measures arerequired to protect against surges.If shielded cables are not used, surge pulses (as defined in EN 61000-4-5) on digital inputsmay be read as a temporary 1 signal due to the short cycle time of <strong>HIMax</strong> systems.Use noise blanking to avoid these types of faults: a signal must be present for at least twocycles before it is evaluated. At the same time, the safety time must not be exceeded.HI 801 003 D Rev.2.0 Page 31 of 70