5 System Bus Module <strong>HIMax</strong>WARNINGPhysical injury possible!SILworX must be used to verify the parameterization.Proceed as follows:• In SILworX, log in to the system module located in Base Plate 0, Slot 2.• In SILworX, log in to the system module on Base Plate 1, Slot 2.• Check the Control Panels of both system bus modules to ensure that the"responsible" attribute has only been set for the correct system bus module (seeFigure 1 and Figure 2)!Re<strong>com</strong>mended Configurations:• If processor modules are only contained on Base Plate 0, both system bus modules onBase Plate 0 must be set to 'responsible' (Figure 1).• If processor modules are also contained on Base Plate 1 (Figure 2), the followingsystem bus modules must be set to 'responsible'.- on Base Plate 0, the system bus module in Slot 1.- on Base Plate 1, the system bus module in Slot 2.Base Plate 0: Base Plate 0R System Bus Module set to ResponsibleBase Plate 1: Base Plate 1Figure 1: Re<strong>com</strong>mended Configuration: All Processor Modules on Base Plate 0Page 26 of 70HI 801 003 D Rev.2.0