<strong>Standard</strong> <strong>Technical</strong> <strong>Features</strong> <strong>of</strong> <strong>BTG</strong> <strong>System</strong> <strong>for</strong> <strong>Supercritical</strong> <strong>660</strong>/800 MW Thermal Units20.3 Low capacity PRDS shall be sized <strong>for</strong> auxiliary steam requirement <strong>of</strong> about 20TPH including <strong>for</strong> requirement <strong>of</strong> fuel oil heating and air conditioning plant (ifrequired) and shall supply steam <strong>for</strong> normal continuous requirements <strong>of</strong> itsown unit.20.4 Sharing <strong>of</strong> Load requirement between high capacity station header and lowcapacity station header shall be possible in case low capacity PRDS is unableto meet Auxiliary steam requirement on its own. The change over from highcapacity PRDS to low capacity PRDS & vice verse shall be automatic.188