Standard Technical Features of BTG System for Supercritical 660 ...
Standard Technical Features of BTG System for Supercritical 660 ... Standard Technical Features of BTG System for Supercritical 660 ...
Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Unitsiii) Adjustable steady state speed regulation shall be provided between3% to 8% of rated speed.iv)Dead band at rated speed and at any power output within rated outputshall not exceed 0.06% of rated speed.12.12 Turbine Protective Devices12.12.1 Emergency governori) A separately actuated over speed device called emergency governorshall be provided to trip the Unit at about 110% of rated speed in casespeed governor fails to limit the turbine overspeed.ii)iii)The emergency governor resetting shall be as per manufacturer'sstandard practice. However, it shall meet the IEC-45 requirements foroverspeed trip.Means for testing the operation of emergency governor shall beprovided to test operation when the machine is on load withoutexceeding the rated speed of the unit.12.12.2 Emergency hand trip deviceTurbine shall be provided with an emergency hand trip device to facilitatemanual tripping of the unit from local along-with facility to trip turbine fromunit control room.12.12.3 Other protective devicesOther turbine protection devices including vacuum trip device, thrust bearingtrip device shall be provided as per standard practices of the manufacturer.12.13 Unloading Devices12.13.1 Low vacuum unloading deviceA low vacuum unloading device shall be provided (if applicable, based onstandard proven practice of the OEM for the unit size in consideration),which shall ensure progressive decrease of steam flow to turbine below apreset value of condenser vacuum, thus restoring the condenser vacuum.12.13.2 Vacuum breakerA D.C. operated device shall be provided for rapid reduction of vacuum incondenser for turbine rotor to be brought to rest as quickly as possible.95
Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units12.14 Turbine Lubrication Oil SystemA self contained lubrication oil system shall be provided for each TG Unitconsisting of:i) Centrifugal/ gear type, main oil pump (MOP) directly driven by turbineshaft or by an AC motor as per manufacturer’s standard practice withcapacity to cater lube oil for bearings & emergency seal oilrequirement. In addition to above, minimum 1x100% AC Aux. oilpump shall be provided for start up, shut down of TG unit and asstandby to MOP for automatic operation catering for requirement oflubricating oil, jacking oil & turning gear oil.ii)iii)iv)One DC motor driven emergency oil pump with sufficient capacity formeeting lubricating oil requirement of bearings during emergency.1x100% capacity each AC & DC jacking oil pumps.Unit lube oil tank of SS with capacity to allow 5 to 8 oil changes perhour (at normal operating level), fitted with non-corrodable strainer and2x100% duty vapour extraction fans driven by explosion proof motors.v) 2x100% DM water cooled lub oil coolers of tube & shell type designedas per TEMA or plate type designed as per relevant codes. The coolersshall be provided with 15% excess heat transfer surface area and withoil pressure greater than water pressure.vi)Piping and all other components of the system coming in contact withoil shall be of stainless steel.12.15 Turbine Lubricating Oil Purification SystemEach T.G. unit shall be provided with a permanently connected, continuousoil purification system comprising of following major equipment:i) Oil purification system shall be of either centrifuge type or coalescingtype as per proven standard design of OEM and shall have the capacityto purify 20% of total oil charge in system per hour. The purified oilshall have maximum particle size conforming to code 15/12 as per ISO4406 and moisture content not more than 500 ppm or as perrequirement of the turbine manufacturer which ever is more stringent.The above purity shall be achievable with particle size and moisturecontent of inlet oil conforming to code 21/18 as per ISO 4406 and15000 ppm respectively in one pass.ii)Carbon steel anti-flood tank, applicable for centrifuge type purifier.iii) Positive displacement feed & discharge pumps (if required), eachhaving capacity 10% higher than purifying unit.96
- Page 57 and 58: Standard Technical Features of BTG
- Page 59 and 60: Standard Technical Features of BTG
- Page 61 and 62: Standard Technical Features of BTG
- Page 63 and 64: Standard Technical Features of BTG
- Page 65 and 66: Standard Technical Features of BTG
- Page 67 and 68: Standard Technical Features of BTG
- Page 69 and 70: Standard Technical Features of BTG
- Page 71 and 72: Standard Technical Features of BTG
- Page 73 and 74: Standard Technical Features of BTG
- Page 75 and 76: Standard Technical Features of BTG
- Page 77 and 78: Standard Technical Features of BTG
- Page 79 and 80: Standard Technical Features of BTG
- Page 81 and 82: Standard Technical Features of BTG
- Page 83 and 84: Standard Technical Features of BTG
- Page 85 and 86: Standard Technical Features of BTG
- Page 87 and 88: Standard Technical Features of BTG
- Page 89 and 90: Standard Technical Features of BTG
- Page 91 and 92: Standard Technical Features of BTG
- Page 93 and 94: Standard Technical Features of BTG
- Page 95 and 96: Standard Technical Features of BTG
- Page 97 and 98: Standard Technical Features of BTG
- Page 99 and 100: Standard Technical Features of BTG
- Page 101 and 102: Standard Technical Features of BTG
- Page 103 and 104: Standard Technical Features of BTG
- Page 105 and 106: Standard Technical Features of BTG
- Page 107: Standard Technical Features of BTG
- Page 111 and 112: Standard Technical Features of BTG
- Page 113 and 114: Standard Technical Features of BTG
- Page 115 and 116: Standard Technical Features of BTG
- Page 117 and 118: Standard Technical Features of BTG
- Page 119 and 120: Standard Technical Features of BTG
- Page 121 and 122: Standard Technical Features of BTG
- Page 123 and 124: Standard Technical Features of BTG
- Page 125 and 126: Standard Technical Features of BTG
- Page 127 and 128: Standard Technical Features of BTG
- Page 129 and 130: Standard Technical Features of BTG
- Page 131 and 132: Standard Technical Features of BTG
- Page 133 and 134: Standard Technical Features of BTG
- Page 135 and 136: Standard Technical Features of BTG
- Page 137 and 138: Standard Technical Features of BTG
- Page 139 and 140: Standard Technical Features of BTG
- Page 141 and 142: Standard Technical Features of BTG
- Page 143 and 144: Standard Technical Features of BTG
- Page 145 and 146: Standard Technical Features of BTG
- Page 148 and 149: Standard Technical Features of BTG
- Page 150 and 151: Standard Technical Features of BTG
- Page 152 and 153: Standard Technical Features of BTG
- Page 154 and 155: Standard Technical Features of BTG
- Page 156 and 157: Standard Technical Features of BTG
<strong>Standard</strong> <strong>Technical</strong> <strong>Features</strong> <strong>of</strong> <strong>BTG</strong> <strong>System</strong> <strong>for</strong> <strong>Supercritical</strong> <strong>660</strong>/800 MW Thermal Units12.14 Turbine Lubrication Oil <strong>System</strong>A self contained lubrication oil system shall be provided <strong>for</strong> each TG Unitconsisting <strong>of</strong>:i) Centrifugal/ gear type, main oil pump (MOP) directly driven by turbineshaft or by an AC motor as per manufacturer’s standard practice withcapacity to cater lube oil <strong>for</strong> bearings & emergency seal oilrequirement. In addition to above, minimum 1x100% AC Aux. oilpump shall be provided <strong>for</strong> start up, shut down <strong>of</strong> TG unit and asstandby to MOP <strong>for</strong> automatic operation catering <strong>for</strong> requirement <strong>of</strong>lubricating oil, jacking oil & turning gear oil.ii)iii)iv)One DC motor driven emergency oil pump with sufficient capacity <strong>for</strong>meeting lubricating oil requirement <strong>of</strong> bearings during emergency.1x100% capacity each AC & DC jacking oil pumps.Unit lube oil tank <strong>of</strong> SS with capacity to allow 5 to 8 oil changes perhour (at normal operating level), fitted with non-corrodable strainer and2x100% duty vapour extraction fans driven by explosion pro<strong>of</strong> motors.v) 2x100% DM water cooled lub oil coolers <strong>of</strong> tube & shell type designedas per TEMA or plate type designed as per relevant codes. The coolersshall be provided with 15% excess heat transfer surface area and withoil pressure greater than water pressure.vi)Piping and all other components <strong>of</strong> the system coming in contact withoil shall be <strong>of</strong> stainless steel.12.15 Turbine Lubricating Oil Purification <strong>System</strong>Each T.G. unit shall be provided with a permanently connected, continuousoil purification system comprising <strong>of</strong> following major equipment:i) Oil purification system shall be <strong>of</strong> either centrifuge type or coalescingtype as per proven standard design <strong>of</strong> OEM and shall have the capacityto purify 20% <strong>of</strong> total oil charge in system per hour. The purified oilshall have maximum particle size con<strong>for</strong>ming to code 15/12 as per ISO4406 and moisture content not more than 500 ppm or as perrequirement <strong>of</strong> the turbine manufacturer which ever is more stringent.The above purity shall be achievable with particle size and moisturecontent <strong>of</strong> inlet oil con<strong>for</strong>ming to code 21/18 as per ISO 4406 and15000 ppm respectively in one pass.ii)Carbon steel anti-flood tank, applicable <strong>for</strong> centrifuge type purifier.iii) Positive displacement feed & discharge pumps (if required), eachhaving capacity 10% higher than purifying unit.96