Standard Technical Features of BTG System for Supercritical 660 ...
Standard Technical Features of BTG System for Supercritical 660 ... Standard Technical Features of BTG System for Supercritical 660 ...
Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Unitsmanufacturer. In such case VWO shall mean wide open condition of theturbine main control valves and the overload valves.ii)iii)iv)The turbine- generator set shall be capable of continuous TMCR outputunder rated steam conditions, 89 mm Hg (abs) 3 condenser pressure, 1%make-up and 47.5 Hz grid frequency.The steam turbine generator unit shall be suitable for direct connectionto steam generator having no inter connection with other units either onthe boiler feed water side or main steam side.The steam turbine shall have preferably seven uncontrolled extractionsfor regenerative feed heating based on optimized cycle and shall besuitable for satisfactory operation under tropical conditions. The cycleshall consist of minimum 3 nos. of HP heaters with extraction for top HPheater from HP turbine, one no. of deaerator and minimum 3 nos. of LPheaters.12.1.4 Operational capabilitiesi) Overpressure Operation (if applicable): Turbine overpressure capability(under VWO) shall be indicated along with corresponding continuousoutput of TG set. The Turbine shall be capable of accepting variation insteam pressure as per IEC-45.ii)iii)iv)HP Heaters Out of Service: Turbine shall be capable of continuousoperation under all HP heaters out of service with maximum output notless than rated output.Variable Pressure Operation: Turbine shall be capable of operating onvariable pressure mode during part load and start-up operation.Two Shift & Cyclic Load Operation: The Turbine shall be suitable fortwo-shift operation & cyclic load variations.v) Fast Start- up and Loading/ Unloading Rate: The TG set shall becapable of being started from cold condition to full load operatingconditions in as short time as possible. The TG set shall be designed forminimum rate of loading/ unloading mentioned below withoutcompromising on design life of the machine:a) Step load change : Minimum ± 10% to facilitate fast loading/unloading of the unit.b) Ramp Rate : Minimum ± 3% per minute above 30% load.3 70mmHg (abs) for sea water based once through CW system89
Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Unitsvi)vii)House- load Operation: The TG set shall be capable of operating onHouse load using HP-LP bypass system during sudden total exportload throw off. Unit shall not trip on overspeed in the event of totalexport load throw-off.No. of Start- ups: Expected number of turbine generator start-upsduring design life of minimum 25 years shall be as under. The designof turbine generator and the associated systems shall take care of thesestart ups without affecting the life of equipment adversely. Nocomponent shall be stressed beyond acceptable safe stress and fatiguelevels when operating under the stated duty conditions.a) Cold Start (after shut down period exceeding 72hours)b) Warm Start (after shut down period between 10hours and 72 hours)c) Hot Start (after shut down period less than 10hours)1501000400012.1.5 Material requirementsThe steam turbine shall be built-up using materials which are field proven.12.1.6 Maintenance requirementsi) Wet Steam Washing (if applicable): Necessary stubs/ connections onturbine/piping shall be provided for future connection to wet steamwashing system, if applicable, as per standard practice of turbinemanufacturer.ii) Fast Cooling of Turbine: Provision shall be made to facilitate fastcooling of turbine during emergency condition for quick access.iii)iv)Boroscopic Inspection: Boroscopic Inspection ports shall be provided inturbine for in situ inspection of turbine internals as per standard practice.The inspection ports shall cover turbine internals as maximum aspossible as per manufacturer Standard practice. The inspection portshould be designed for ease of accessibility with leakage proof featureswhile in operation.Preservation System: Turbine preservation system shall be provided toprotect against corrosion during idle periods as per OEM practice.12.2 Turbine CasingThe turbine casing design shall have following features:i) Symmetrical in design to minimize effects of thermal stress and creep.90
- Page 51 and 52: Standard Technical Features of BTG
- Page 53 and 54: Standard Technical Features of BTG
- Page 55 and 56: Standard Technical Features of BTG
- Page 57 and 58: Standard Technical Features of BTG
- Page 59 and 60: Standard Technical Features of BTG
- Page 61 and 62: Standard Technical Features of BTG
- Page 63 and 64: Standard Technical Features of BTG
- Page 65 and 66: Standard Technical Features of BTG
- Page 67 and 68: Standard Technical Features of BTG
- Page 69 and 70: Standard Technical Features of BTG
- Page 71 and 72: Standard Technical Features of BTG
- Page 73 and 74: Standard Technical Features of BTG
- Page 75 and 76: Standard Technical Features of BTG
- Page 77 and 78: Standard Technical Features of BTG
- Page 79 and 80: Standard Technical Features of BTG
- Page 81 and 82: Standard Technical Features of BTG
- Page 83 and 84: Standard Technical Features of BTG
- Page 85 and 86: Standard Technical Features of BTG
- Page 87 and 88: Standard Technical Features of BTG
- Page 89 and 90: Standard Technical Features of BTG
- Page 91 and 92: Standard Technical Features of BTG
- Page 93 and 94: Standard Technical Features of BTG
- Page 95 and 96: Standard Technical Features of BTG
- Page 97 and 98: Standard Technical Features of BTG
- Page 99 and 100: Standard Technical Features of BTG
- Page 101: Standard Technical Features of BTG
- Page 105 and 106: Standard Technical Features of BTG
- Page 107 and 108: Standard Technical Features of BTG
- Page 109 and 110: Standard Technical Features of BTG
- Page 111 and 112: Standard Technical Features of BTG
- Page 113 and 114: Standard Technical Features of BTG
- Page 115 and 116: Standard Technical Features of BTG
- Page 117 and 118: Standard Technical Features of BTG
- Page 119 and 120: Standard Technical Features of BTG
- Page 121 and 122: Standard Technical Features of BTG
- Page 123 and 124: Standard Technical Features of BTG
- Page 125 and 126: Standard Technical Features of BTG
- Page 127 and 128: Standard Technical Features of BTG
- Page 129 and 130: Standard Technical Features of BTG
- Page 131 and 132: Standard Technical Features of BTG
- Page 133 and 134: Standard Technical Features of BTG
- Page 135 and 136: Standard Technical Features of BTG
- Page 137 and 138: Standard Technical Features of BTG
- Page 139 and 140: Standard Technical Features of BTG
- Page 141 and 142: Standard Technical Features of BTG
- Page 143 and 144: Standard Technical Features of BTG
- Page 145 and 146: Standard Technical Features of BTG
- Page 148 and 149: Standard Technical Features of BTG
- Page 150 and 151: Standard Technical Features of BTG
<strong>Standard</strong> <strong>Technical</strong> <strong>Features</strong> <strong>of</strong> <strong>BTG</strong> <strong>System</strong> <strong>for</strong> <strong>Supercritical</strong> <strong>660</strong>/800 MW Thermal Unitsvi)vii)House- load Operation: The TG set shall be capable <strong>of</strong> operating onHouse load using HP-LP bypass system during sudden total exportload throw <strong>of</strong>f. Unit shall not trip on overspeed in the event <strong>of</strong> totalexport load throw-<strong>of</strong>f.No. <strong>of</strong> Start- ups: Expected number <strong>of</strong> turbine generator start-upsduring design life <strong>of</strong> minimum 25 years shall be as under. The design<strong>of</strong> turbine generator and the associated systems shall take care <strong>of</strong> thesestart ups without affecting the life <strong>of</strong> equipment adversely. Nocomponent shall be stressed beyond acceptable safe stress and fatiguelevels when operating under the stated duty conditions.a) Cold Start (after shut down period exceeding 72hours)b) Warm Start (after shut down period between 10hours and 72 hours)c) Hot Start (after shut down period less than 10hours)1501000400012.1.5 Material requirementsThe steam turbine shall be built-up using materials which are field proven.12.1.6 Maintenance requirementsi) Wet Steam Washing (if applicable): Necessary stubs/ connections onturbine/piping shall be provided <strong>for</strong> future connection to wet steamwashing system, if applicable, as per standard practice <strong>of</strong> turbinemanufacturer.ii) Fast Cooling <strong>of</strong> Turbine: Provision shall be made to facilitate fastcooling <strong>of</strong> turbine during emergency condition <strong>for</strong> quick access.iii)iv)Boroscopic Inspection: Boroscopic Inspection ports shall be provided inturbine <strong>for</strong> in situ inspection <strong>of</strong> turbine internals as per standard practice.The inspection ports shall cover turbine internals as maximum aspossible as per manufacturer <strong>Standard</strong> practice. The inspection portshould be designed <strong>for</strong> ease <strong>of</strong> accessibility with leakage pro<strong>of</strong> featureswhile in operation.Preservation <strong>System</strong>: Turbine preservation system shall be provided toprotect against corrosion during idle periods as per OEM practice.12.2 Turbine CasingThe turbine casing design shall have following features:i) Symmetrical in design to minimize effects <strong>of</strong> thermal stress and creep.90