9-5-6. Only 4-Way valve does not operate (During heating operation)Heat Pump ModelFILE NO. SVM-05020Shut off the power supplyfrom AC outlet once andturn it on after 5 seconds.Does the OPERATION lamp blink?NOSee "Power can not be turned on".YESDoes the power turn on bypushing the [START/STOP] buttonof the remote control?NOSee "Power can not be turned on".YESIs the voltage across the indoor terminal( 2 - 3 ) 220-240V?NORelays (RY04) or IC31or IC30 is failure.Replace the P.C.board.YESIs cable connection between indoorand outdoor units correct?NOCorrect cabling between indoorand outdoor units.YESIs the voltage across the outdoor terminal( 2 - 3 ) 220-240V?NOCables between indoorand outddor units are defective.YESIs the wiring of solenoid coil for4-way valve normal?NOSolenoid coil is defective.YES4-way valve is defective.−63 −