AIR CONDITIONER - Heronhill Air Conditioning Ltd
AIR CONDITIONER - Heronhill Air Conditioning Ltd
AIR CONDITIONER - Heronhill Air Conditioning Ltd
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
FILE NO. SVM-050205-5. RAS-07UKP-ES4 / RAS-07UA-ES4CoolingIndoor unitHeat exchangerT10.39m(Connecting pipe)∅9.52Cross flow fan0.49m(Connecting pipe)∅6.35O.D.:9.52mmPO.D.:6.35mmPacked valve(∅9.52)Packed valve(∅6.35)CoolingCooling CompressorPA82X1C-4DZDNCapillary tube∅1.2x550lHeat exchangerRefrigerantCoolingPropeller fanOutdoor unitMark(R-410A : 0.63 kg.)means check points of Gas Leak.50HzStandardpressure P(MPaG)Surface temp. of heatexchanger interchangingpipe T1 (°C)Fan speed(indoor)Ambient temp.conditions DB/WB(°C)IndoorOutdoorStandard 1.00 13.0 High 27/19 35/24Cooling Overload 1.14 18.0 High 32/23 43/26Low temperature 0.75 2.0 Low 21/15 21/15Note :• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)− 23 −