FILE NO. SVM-050205-4. RAS-10UKP-ES4 / RAS-10UA-ES4CoolingIndoor unitHeat exchangerT10.39m(Connecting pipe)∅9.52Cross flow fan0.49m(Connecting pipe)∅6.35O.D.:9.52mmPO.D.:6.35mmPacked valve(∅9.52)Packed valve(∅6.35)CoolingCooling CompressorPA108X1C-4FZDNCapillary tube∅1.5x1100lHeat exchangerRefrigerantCoolingPropeller fanOutdoor unitMark(R410A : 0.70 kg.)means check points of Gas Leak.50HzStandardpressure P(MPaG)Surface temp. of heatexchanger interchangingpipe T1 (°C)Fan speed(indoor)Ambient temp.conditions DB/WB(°C)IndoorOutdoorStandard 0.98 11.0 High 27/19 35/24Cooling Overload 1.10 15.0 High 32/23 43/26Low temperature 0.85 5.0 Low 21/15 21/15Note :•Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)−22−