<strong>Servicing</strong> Practices<br />
Moisture removal<br />
EXHAUST<br />
OPEN<br />
OPEN<br />
OPEN<br />
VACUUM PUMP<br />
8 - In case <strong>of</strong> closed solenoid valves in the system,<br />
air is usually trapped in-between valves where<br />
they should be opened manually if supplied<br />
with open screws, by applying direct electrical<br />
source to solenoid coil, or by using a service<br />
hand magnet.<br />
9 - Charging <strong>of</strong> refrigerant can now begin, either<br />
direct to the high-pressure liquid side or<br />
charging into the suction side when the<br />
compressor is running.<br />
94