01.12.2012 Views

Manual for Refrigeration Servicing Technicians - UNEP - Division of ...

Manual for Refrigeration Servicing Technicians - UNEP - Division of ...

Manual for Refrigeration Servicing Technicians - UNEP - Division of ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3<br />

Refrigerant Management<br />

CHAPITRE 3<br />

PAGE 24<br />

Recovery from a domestic refrigerator<br />

It is possible to recover refrigerant from a hermetically sealed<br />

system, which has no service valve. A line-tap valve (piercing<br />

valve) should be fitted to the system, and a recovery unit used to<br />

remove the refrigerant from the unit via the line-tap as with the<br />

larger system. Line-tap valves should never be left permanently in<br />

place, but removed after use if placed on the process tube (if the<br />

equipment is going <strong>for</strong> disposal). Because <strong>of</strong> the small charge <strong>of</strong><br />

refrigerant, only vapour recovery is needed.<br />

It is recommended to install tap-valves on both and low pressure side, as<br />

shown here:<br />

Recovery from a domestic refrigerator<br />

Recovery from commercial cold room system<br />

Liquid transfer<br />

Connect the recovery cylinder’s hose to the system’s outlet stop<br />

valve on the condenser/receiver. To control liquid flow, install a<br />

sight glass to the hose and cylinder. From the recovery cylinder’s<br />

vapour side, use a drier. Outlet/discharge side <strong>of</strong> the recovery unit<br />

goes to the system’s high-pressure side at the inlet condenser<br />

or compressor high-pressure stop valve. All <strong>of</strong> the system’s stop<br />

valves have to be opened, including the solenoid valves.<br />

Run the recovery unit and keep an eye on the sight glass. When<br />

there is no more liquid transferred through the sight glass, and there<br />

is no icing left on the compressor shell, on the receiver or anywhere<br />

else, this indicates there is negligible amounts <strong>of</strong> refrigerant left in<br />

the system.<br />

Vapour transfer<br />

When liquid transfer is completed, connect the hoses from the<br />

recovery unit suction/inlet side to the compressor low or highpressure<br />

side. For better recovery, connect hoses to both the high<br />

and low pressure sides using a service manifold. The recovery<br />

discharge/outlet side should be connected to the recovery<br />

cylinder’s vapour side. Be sure that all service/shut <strong>of</strong>f valves are<br />

open to avoid “locking” refrigerant into the system.<br />

81

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!