Manual for Refrigeration Servicing Technicians - UNEP - Division of ...
Manual for Refrigeration Servicing Technicians - UNEP - Division of ...
Manual for Refrigeration Servicing Technicians - UNEP - Division of ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
3<br />
Refrigerant Management<br />
CHAPITRE 3<br />
PAGE 24<br />
Recovery from a domestic refrigerator<br />
It is possible to recover refrigerant from a hermetically sealed<br />
system, which has no service valve. A line-tap valve (piercing<br />
valve) should be fitted to the system, and a recovery unit used to<br />
remove the refrigerant from the unit via the line-tap as with the<br />
larger system. Line-tap valves should never be left permanently in<br />
place, but removed after use if placed on the process tube (if the<br />
equipment is going <strong>for</strong> disposal). Because <strong>of</strong> the small charge <strong>of</strong><br />
refrigerant, only vapour recovery is needed.<br />
It is recommended to install tap-valves on both and low pressure side, as<br />
shown here:<br />
Recovery from a domestic refrigerator<br />
Recovery from commercial cold room system<br />
Liquid transfer<br />
Connect the recovery cylinder’s hose to the system’s outlet stop<br />
valve on the condenser/receiver. To control liquid flow, install a<br />
sight glass to the hose and cylinder. From the recovery cylinder’s<br />
vapour side, use a drier. Outlet/discharge side <strong>of</strong> the recovery unit<br />
goes to the system’s high-pressure side at the inlet condenser<br />
or compressor high-pressure stop valve. All <strong>of</strong> the system’s stop<br />
valves have to be opened, including the solenoid valves.<br />
Run the recovery unit and keep an eye on the sight glass. When<br />
there is no more liquid transferred through the sight glass, and there<br />
is no icing left on the compressor shell, on the receiver or anywhere<br />
else, this indicates there is negligible amounts <strong>of</strong> refrigerant left in<br />
the system.<br />
Vapour transfer<br />
When liquid transfer is completed, connect the hoses from the<br />
recovery unit suction/inlet side to the compressor low or highpressure<br />
side. For better recovery, connect hoses to both the high<br />
and low pressure sides using a service manifold. The recovery<br />
discharge/outlet side should be connected to the recovery<br />
cylinder’s vapour side. Be sure that all service/shut <strong>of</strong>f valves are<br />
open to avoid “locking” refrigerant into the system.<br />
81