3<br />
Refrigerant Management<br />
Using the system’s own compressor<br />
If the refrigerant in a system is to be removed and the system has a<br />
working compressor, it is possible to use the compressor to recover<br />
the refrigerant. It may be possible to pump the system down in the<br />
normal way and then decant the refrigerant into a cooled recovery<br />
cylinder, or it may only be possible to use the cooled recovery<br />
cylinder as both condenser and receiver by installing it at the<br />
compressor outlet, as shown in this diagram.<br />
Capillary tube<br />
Closed<br />
Filter-drier<br />
Compressor<br />
operating<br />
Open<br />
Vapor valve<br />
open<br />
Recovery Cylinder<br />
packed in ice<br />
Using the compressor<br />
to recover the refrigerant<br />