Manual for Refrigeration Servicing Technicians - UNEP - Division of ...
Manual for Refrigeration Servicing Technicians - UNEP - Division of ...
Manual for Refrigeration Servicing Technicians - UNEP - Division of ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
5<br />
Retr<strong>of</strong>itting<br />
7 - If the refrigerant to be added to the system is incompatible with<br />
the existing oil (typically a mineral oil) then it must be removed<br />
(otherwise, this stage can be ignored). Drain and recover the<br />
existing mineral oil charge, measure the quantity and compare<br />
with the recommended oil charge to determine the quantity <strong>of</strong> oil<br />
left in the system. A major problem with retr<strong>of</strong>its is removing the<br />
residual mineral oil. This is important because enough mineral oil<br />
is not removed, it can deposit on the evaporator heat exchanger<br />
surfaces, severely degrading per<strong>for</strong>mance. Since many small<br />
hermetic compressors do not have oil drains, removal <strong>of</strong> the<br />
compressor from the system may be necessary <strong>for</strong> draining the<br />
lubricant. The best point in the system to drain the lubricant is<br />
the suction line <strong>of</strong> the compressor. Small hand-operated pumps<br />
are available which permit insertion <strong>of</strong> a tube into the compressor<br />
access port <strong>for</strong> removal <strong>of</strong> the mineral oil without removing<br />
the compressor from the system. Remember that most <strong>of</strong> the<br />
mineral oil must be removed from the system be<strong>for</strong>e adding the<br />
replacement lubricant.<br />
8 - Replace all equipment components and accessories that will be<br />
affected by the new alternative refrigerant and the refrigerant oil<br />
suitable <strong>for</strong> the new alternative refrigerant e.g. expansion valve,<br />
gaskets, filter drier, etc., as recommended by the manufacturer.<br />
Most CFC or HCFC systems with expansion valves will operate<br />
satisfactorily, however, it may be necessary to adjust the superheat.<br />
If the system uses a capillary tube, it will need to be replaced with<br />
one <strong>of</strong> greater or lesser restriction in order to achieve satisfactory<br />
per<strong>for</strong>mance over the complete range <strong>of</strong> design conditions. It is<br />
recommended that the technician consults with the equipment<br />
manufacturer be<strong>for</strong>e replacing the capillary tube.<br />
9 - Charge the system with new and correct amount <strong>of</strong> alternative<br />
refrigerant oil as recommended by compressor/system manufacturer.<br />
10 - Reinstall the compressor following the standard service practices<br />
recommended by the manufacturer. If an oil pump was used to<br />
remove the oil, reseal the access port.<br />
11 - Run the system while per<strong>for</strong>ming the oil change procedure as many<br />
times as necessary until the mineral oil in the system does not<br />
exceed the recommended 5% acceptable level. Test kits are<br />
available from several lubricant suppliers that check <strong>for</strong> residual<br />
mineral oil content. Generally, it will require about three charges to<br />
get the mineral oil content down to the acceptable level.<br />
12 - Leak test the system with oxygen-free dry nitrogen and observe a<br />
24-hour standing pressure. Make corrections if deemed necessary.<br />
13 - Evacuate system to at least 1000 microns (1 mbar, 29.87 in Hg)<br />
using an appropriate vacuum pump and an electronic vacuum<br />
gauge. Use normal service practices to reconnect and evacuate the<br />
system, to remove air and other non-condensable contaminants.<br />
14 - Charge the system with the appropriate amount <strong>of</strong> alternative<br />
refrigerant. This can normally be approximated by using the ratio<br />
<strong>of</strong> liquid densities at the condensing temperature. When charging<br />
the system with alternative refrigerant, use the same charging<br />
114