01.12.2012 Views

Manual for Refrigeration Servicing Technicians - UNEP - Division of ...

Manual for Refrigeration Servicing Technicians - UNEP - Division of ...

Manual for Refrigeration Servicing Technicians - UNEP - Division of ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

5<br />

Retr<strong>of</strong>itting<br />

7 - If the refrigerant to be added to the system is incompatible with<br />

the existing oil (typically a mineral oil) then it must be removed<br />

(otherwise, this stage can be ignored). Drain and recover the<br />

existing mineral oil charge, measure the quantity and compare<br />

with the recommended oil charge to determine the quantity <strong>of</strong> oil<br />

left in the system. A major problem with retr<strong>of</strong>its is removing the<br />

residual mineral oil. This is important because enough mineral oil<br />

is not removed, it can deposit on the evaporator heat exchanger<br />

surfaces, severely degrading per<strong>for</strong>mance. Since many small<br />

hermetic compressors do not have oil drains, removal <strong>of</strong> the<br />

compressor from the system may be necessary <strong>for</strong> draining the<br />

lubricant. The best point in the system to drain the lubricant is<br />

the suction line <strong>of</strong> the compressor. Small hand-operated pumps<br />

are available which permit insertion <strong>of</strong> a tube into the compressor<br />

access port <strong>for</strong> removal <strong>of</strong> the mineral oil without removing<br />

the compressor from the system. Remember that most <strong>of</strong> the<br />

mineral oil must be removed from the system be<strong>for</strong>e adding the<br />

replacement lubricant.<br />

8 - Replace all equipment components and accessories that will be<br />

affected by the new alternative refrigerant and the refrigerant oil<br />

suitable <strong>for</strong> the new alternative refrigerant e.g. expansion valve,<br />

gaskets, filter drier, etc., as recommended by the manufacturer.<br />

Most CFC or HCFC systems with expansion valves will operate<br />

satisfactorily, however, it may be necessary to adjust the superheat.<br />

If the system uses a capillary tube, it will need to be replaced with<br />

one <strong>of</strong> greater or lesser restriction in order to achieve satisfactory<br />

per<strong>for</strong>mance over the complete range <strong>of</strong> design conditions. It is<br />

recommended that the technician consults with the equipment<br />

manufacturer be<strong>for</strong>e replacing the capillary tube.<br />

9 - Charge the system with new and correct amount <strong>of</strong> alternative<br />

refrigerant oil as recommended by compressor/system manufacturer.<br />

10 - Reinstall the compressor following the standard service practices<br />

recommended by the manufacturer. If an oil pump was used to<br />

remove the oil, reseal the access port.<br />

11 - Run the system while per<strong>for</strong>ming the oil change procedure as many<br />

times as necessary until the mineral oil in the system does not<br />

exceed the recommended 5% acceptable level. Test kits are<br />

available from several lubricant suppliers that check <strong>for</strong> residual<br />

mineral oil content. Generally, it will require about three charges to<br />

get the mineral oil content down to the acceptable level.<br />

12 - Leak test the system with oxygen-free dry nitrogen and observe a<br />

24-hour standing pressure. Make corrections if deemed necessary.<br />

13 - Evacuate system to at least 1000 microns (1 mbar, 29.87 in Hg)<br />

using an appropriate vacuum pump and an electronic vacuum<br />

gauge. Use normal service practices to reconnect and evacuate the<br />

system, to remove air and other non-condensable contaminants.<br />

14 - Charge the system with the appropriate amount <strong>of</strong> alternative<br />

refrigerant. This can normally be approximated by using the ratio<br />

<strong>of</strong> liquid densities at the condensing temperature. When charging<br />

the system with alternative refrigerant, use the same charging<br />

114

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!