GEIndustrial<strong>12</strong>-<strong>24kV</strong> <strong>Vacuum</strong> <strong>Circuit</strong> <strong>Breaker</strong>GE imagination at work


SecoVac <strong>12</strong>-<strong>24kV</strong>Product Performance Features2420156191. Tulip Contact2. Contact Arm11. Insulated Coupling Rod<strong>12</strong>. Opening Spring73. Lower Contact Terminal13. Earthing Contact of Cart8184. Upper Contact Terminal14. Classis of Cart9175. Embedded Pole6. <strong>Vacuum</strong> Interrupter15. Hole for Driving Screw16. Locking Piece1167. Moving contact pieces8. Metal Bellows17. Operating Shaft18. Operation Cover29. Disc Spring for Contact Pressure19. Closing Spring10. Shutter Driving Plate20. Secondary Plug310 11 <strong>12</strong> 13 14 15Unique and Proven Embedded Pole TechnologySecoVac series MV embedded pole vacuum circuit breaker uses the latest and mature technology of Automatic Pressure Gelation (APG) to embed the vacuuminterrupter and connection terminals within epoxy resin. The vacuum interrupter is cast in the epoxy resin, so inside the epoxy resin there is no screw fixationthat will cause the concentrated harsh electrical field inside the epoxy resin and will consequently result in decrease of the electrical insulation strength of thepole. Thanks to the embedded pole technology, the assembly of the pole is simplified, and the assembly accuracy as well as quality of the embedded pole iseasily to be controlled by the state of the art production process. The embedded pole technology also obviously improve the environmental resistantcapability of the breaker, as the primary circuit of the breaker is completely embedded inside the epoxy resin, the risk of insulation fault caused by adverseoperating environment such as dust, humidity, ingression of small animals, polluted ambient and high altitude operating site are eliminated thoroughly.The key know how of the embedded pole technology is the buffering layer betweenepoxy resin and ceramic housing of vacuum interrupter, the material and processingof the buffering layer is essential to ensure the integrity of epoxy resin of theembedded pole provide adequate adhesion between each other in any circumstance.Our patented LSR (Liquid Silicon Rubber) buffering layer and double APG (AutoPressure Gelation) process adopted in the producing of the embedded polethoroughly eliminates the cracking of the epoxy resin caused by the large differenceof thermal expansion coefficient between epoxy resin and ceramic in case of rapidchanging of the ambient temperature. APG process for LSR buffering layer ensuresthat there will not be any air gap or bubble between the buffering layer and ceramichousing, hence, the high electrical insulation strength of the embedded pole ofSecoVac series MV embedded pole vacuum circuit breaker is guaranteed.The partial discharge value of embedded pole manufactured by our patented LSR(Liquid Silicon Rubber) buffering layer and double APG (Auto Pressure Gelation)process is below 5pc with an applied testing voltage of 1.2Um.SecoVac 02


SecoVac <strong>12</strong>-<strong>24kV</strong>The State of the art Processing and Advanced Quality ControlThe high quality of the embedded pole is achieved by using the latest APG (Auto Pressure Gelation) technology and advanced vacuum mixing and degassingtechnology that are carried out by the equipment. The Vogel clamping machine is an essential piece of equipment to ensure the mechanical and insulatingstrength of the embedded pole of SecoVac series MV embedded pole vacuum circuit breaker.As well as the processing facilities, the testing facilities are also very important to the quality control of the breaker. In the manufacturing process of SecoVacVCB, from incoming material quality control to the final inspection and testing, every step is strictly calibrated and tested by means of testing facilities.For every embedded pole, before it goes into the breaker assembly line, it shall go through following inspections and testing carried out in factory:• X-ray inspection• Power frequency withstand voltage test• Partial discharge measurement• Extremely high and low temperature impulse testBefore delivery, the following tests and inspections will be done forSecoVac series MV embedded pole vacuum circuit breaker in factory bymeans of advanced testing equipments:• Dynamic characteristics measurement• Power frequency withstand voltage testing• Inspection of interlocking system between breaker and withdrawable unit• Secondary wiring inspection• <strong>Circuit</strong> resistance measurementFull Range Product with High Technical ParametersRated voltage up to <strong>24kV</strong>Rated current up to 4000ARated short circuit breaking current up to 50kAMechanical endurance up to 30,000 operating cyclesRated short circuit breaking times up to 50 timesDC component of short circuit breaking current up to 62%Large external creep distance reaches 20mm/kVSecoVac 04


SecoVac <strong>12</strong>-<strong>24kV</strong><strong>Breaker</strong> FeaturesFront PanelThis front panel fits into a collar-frame in the equipment when the breakeris in the CONNECT position. It provides a metal barrier between thebreaker compartment and the secondary device compartment. Wellmarked and easy-to-read operating controls and indicators include TRIPbutton, CLOSE button, OPEN/CLOSE indicator, CHARGE/DISCHRGE indicator,OPERATIONS counter and provision for manual charging the breaker.Primary DisconnectThe primary disconnect finger set is rugged and easy to inspect. Designedfor optimum contact, built of silver-plated copper and tested forcontinuous and short time current. Cycloid design is more convenient toconnect and expand wider contact area than flat design. Thesedisconnects provide proper contact integrity throughout the life of thegear for the critical primary disconnect function.<strong>Breaker</strong> MechanismAll the mechanical parts of the mechanism are integrated into openingand closing modules individually. The closing and opening modules areuniversal to whole series of SecoVac embedded pole vacuum circuitbreaker in spite of the ratings. Such design assures no mechanicalreadjustment after the replacement, thereby not only shortens lead-timebut also reduces operation and maintenance cost.Interlock SystemFor personnel safety, SecoVac is designed with a number of mechanicaland electrical interlocks. For example, breaker contacts must be openbefore the breaker can be moved to or from the CONNECT position. Apositive mechanical stop is provided when the breaker reaches theCONNECT or TEST/DISCONNECT positions. Mechanical interferenceinterlocks are provided to permit only the insertion of properly ratedbreakers into any specific compartment. These and other necessaryinterlocks provide a comprehensive protection system. Furthermore,springs automatically discharge when the breaker is withdrawn from theCONNECT position and breakers cannot be inserted in the closed position.SecoVac 05


SecoVac <strong>12</strong>-<strong>24kV</strong>Technical DataDescriptionUnitRated voltagekV7.2/<strong>12</strong>24Rated currentA630/<strong>12</strong>50/1600/2000/2500/3150/4000630/<strong>12</strong>50/1600/2000/2500Rated powerfrequencywithstandvoltage (1min)kV4265Rated lightningimpulsewithstandvoltage (peakvalues)kV75<strong>12</strong>5Rated shortcircuit breakingcurrentkA20/25/31.5/40/5020/25/31.5Rated short timewithstandcurrent (4S)kA20/25/31.5/40/5020/25/31.5Rated peakwithstandcurrentkA50/63/80/100/<strong>12</strong>550/63/80Rated peakmaking currentkA50/63/80/100/<strong>12</strong>550/63/80Rated shortcircuit currentbreaking timesNo. oftimes5050ElectricalenduranceNo. oftimes274(E2) IEC 62271-100:2006274(E2) IEC 62271-100:2006MechanicalenduranceNo. oftimes3000020000OperatingsequenceO-0.3s-CO-180s-COO-180s-CO-180s-COO-0.3s-CO-180s-COO-180s-CO-180s-CORated auxiliarycontrol voltage*VAC 110/220; DC110/220AC 110/220; DC110/220Opening timems35~7035~70Breaking timems25~3525~35Closing timems40~5040~50*Other voltages are available on request.SecoVac 06


SecoVac <strong>12</strong>-<strong>24kV</strong>Overall Dimension<strong>12</strong>kV SecoVac WithdrawableL42.540 62191547622620520260 20598746303510CD25 3203704E133834383132296200 + 0 - 350A816PP16Journey 8~10mmWidth ofSwitchgear (mm)Parameter (<strong>12</strong>kV)P (mm)A (mm) C (mm) D (mm) E (mm) L (mm)Weight (kg)650630A Isc31.5kA<strong>12</strong>50A Isc31.5kA150 502150 502466466500 503 498500503498105105800630A Isc31.5kA<strong>12</strong>50A Isc31.5kA210 650210 650616616640 653 648640653648<strong>12</strong>0<strong>12</strong>01000630A Isc31.5kA<strong>12</strong>50A Isc31.5kA275 850275 8508<strong>12</strong>8<strong>12</strong>836853844836 853 844130130SecoVac 07


SecoVac <strong>12</strong>-<strong>24kV</strong><strong>12</strong>kV SecoVac WithdrawableL48.5M4)4062.51)1302)R280 310W1653)21.576UCDE19252932 320370383296200+0-3450359.5A 816PP1655Journey 8~10mmWidth ofSwitchgear (mm)Parameter<strong>12</strong>kVP (mm)A (mm) C (mm) D (mm) E (mm) L (mm) W (mm) M (mm) R (mm) U (mm) Weight (kg)<strong>12</strong>50A Isc40kA/50kA210650616640 65364849856846942008001600A Isc50kA210650 616640 653 64879 115684694 2002000A Isc50kA21065061664065364879115684694200<strong>12</strong>50A Isc40kA/50kA2758508<strong>12</strong>836 85384449 85 6846942201600A Isc50kA2758508<strong>12</strong>8368538447911568469422010002000A Isc50kA2500A Isc50kA275275850 8<strong>12</strong> 836 853 844 79 115 684 694 2208508<strong>12</strong>836 8538441091497257352953150A Isc50kA2758508<strong>12</strong>8368538441091497257352954000A* Isc50kA2758508<strong>12</strong>836 853844109149725735295Note:1)The heat radiator is only necessary for SecoVac with rated current equal to higher than 2500A.2)The lifting hook should be remove before SecoVac is put into switchgear panel.3)Contact arm system for SecoVac with rated current upto 2000A.4)Contact arm system for SecoVac with rated current 2500A and above.*The forced fan cooling is necessary when SecoVac with rated current 4000A is installed in metal-enclosed switchgear.SecoVac 08


35SecoVac <strong>12</strong>-<strong>24kV</strong>L - Frame for <strong>12</strong>kV SecoVac WithdrawableG-GG205( H )260705GW688 ( D )PPWidth ofSwitchgear (mm)SecoVacPhase to PhaseDistance (mm)Depth (mm) Height (mm) Width (mm)650630A Isc31.5kA<strong>12</strong>50A Isc31.5kA150150688688705705510510800630A Isc31.5kA<strong>12</strong>50A Isc31.5kA2102106886887057056606601000630A Isc31.5kA<strong>12</strong>50A Isc31.5kA275275688688705705860860SecoVac 09


SecoVac <strong>12</strong>-<strong>24kV</strong>L - Frame for <strong>12</strong>kV SecoVac WithdrawableB-BB280H310WB688( D )PPWidth ofSwitchgear (mm)SecoVac<strong>12</strong>50A Isc = 40kA / 50kAPhase to Phase Depth (mm) Height (mm)Distance (mm)210688850Width (mm)660(mm)498001600A Isc40kA210688850660792000A Isc40kA21068885066079<strong>12</strong>50A Isc = 40kA / 50kA 275 688 860 860 4910001600A Isc40kA275 688 8602000A Isc40kA 275 688 860 86079860792500A Isc40kA 275 688 860 86079SecoVac 10


SecoVac <strong>12</strong>-<strong>24kV</strong>L - Frame for <strong>12</strong>kV SecoVac WithdrawableC-CC280860( H )310109860( W )C688( D )275 275( P ) ( P )Width ofSwitchgear (mm)SecoVacPhase to PhaseDistance (mm)Depth (mm) Height (mm) Width (mm)10003150A Isc50kA275 6888608601000 4000A Isc50kA275688860 860Note: Forced cooling fan is necessary when SecoVac rated 4000ASecoVac 11


SecoVac <strong>12</strong>-<strong>24kV</strong><strong>24kV</strong> SecoVac WithdrawableL42.540325Ø93Ø74151677622775+3079031035CDE1913.525 320383447451±2 2964300 0-3 50A16 P P16Journey 810mmWidth ofSwitchgear (mm)SecoVacP (mm) A (mm) C (mm) D (mm) E (mm) L (mm) Weight (kg)800630A Isc31.5kA<strong>12</strong>50A Isc31.5kA210210650 622650 622646646653653648648<strong>12</strong>5<strong>12</strong>51000630A Isc31.5kA<strong>12</strong>50A Isc31.5kA2758508<strong>12</strong>836 853 844135275 850 8<strong>12</strong> 836 853 844 135SecoVac <strong>12</strong>


SecoVac <strong>12</strong>-<strong>24kV</strong><strong>24kV</strong> SecoVac Withdrawable844492)1)815310Ø109Ø1673)325Ø79Ø13516776228308<strong>12</strong>8368531913.5253203834474441±2296300 0-3 5085016 275275816Journey 810mm1) The heat radiator is only necessary for SecoVac with rated current equal to or higher than 2500A2) Ø109 is adapted for SecoVac with rated current 3150A3) Ø79 is adapted for SecoVac with rated current 1600-2500AWidth ofSwitchgear (mm)SecoVacDimension ofContact1600A Isc31.5kAØ 7910002000A Isc31.5kA2500A Isc31.5kA3150A Isc31.5kAØ 79Ø 79Ø 109SecoVac 13


SecoVac <strong>12</strong>-<strong>24kV</strong>L - Frame for <strong>24kV</strong> SecoVac Withdrawable2102104713101PP2DWWidth ofSwitchgear (mm)8001000SecoVac630A Isc31.5KA<strong>12</strong>50A Isc31.5KA630A Isc31.5KA<strong>12</strong>50A Isc31.5KA1600A Isc31.5KA2000A Isc31.5KA2500A Isc31.5KAPhase-to- phasedistance (mm)210210275275275275275Depth (mm) Height (mm)870 937870870937937870937870937870 937870 937Width (mm)794794994994994994994Caution: Remove support part 1 and 2 before L-Frame in use.SecoVac 14


SecoVac <strong>12</strong>-<strong>24kV</strong>Internal Wiring DiagramOpening circuit2nd opening circuitClose blocking circuitClosing circuitCharging circuitOvercurrentrelease(A phase)Overcurrentrelease(B phase)Over Undercurrent voltagerelease release(C phase)Truck Rack Block magnetClosing monitor circuitService positionTest positionY0Y1Y2Y3Y4Y7-Y9Y10PMV0-V5Notes:1.2.3.Blocking Magnet for withdrawable unit---V0Closing block magnetFirst opening releaseClosing releaseUndervoltage releaseIndirect overcurrent release ( optional )Second opening release ( optional )Manual chargingCharging motorRectifier ( V0 & V5 optional )S1S2S3S8S9K0R0JP1JS1Aux.switch-S1 shown for VCB-mechanism is discharged.VCB in opening and service status.The optional components are not included in basic version if not specified .Auxiliary switch of charging MotorAuxiliary switch of block magnet- Y1Auxiliary switch of VCBAuxiliary switch for test positionAuxiliary switch for service positionAnti-pumping relayResistanceBypass of R0Connector of K0 ( the internal anti-pumpingfunction will be dismissed if it is cut )Withdrawable Installation for AC ControlOpening circuit2nd opening circuitClose blocking circuitClosing circuitCharging circuitOvercurrentrelease(A phase)Overcurrentrelease(B phase)Over Undercurrent voltagerelease release(C phase)Truck Rack Block magnetClosing monitor circuitService positionTest positionY0Y1Y2Y3Y4Y7-Y9Y10PMNotes:1.2.3.Blocking Magnet for withdrawable unit---V0Closing block magnetFirst opening releaseClosing releaseUndervoltage releaseIndirect overcurrent release ( optional )Second opening release ( optional )Manual chargingCharging motorS1S2S3S8S9K0R0JP1JS1Aux.switch-S1 shown for c.b.-mechanism discharged.VCB in opening and service status.The optional components are not includerd in basic version if not specified .Auxiliary switch of charging MotorAuxiliary switch of block magnet- Y1Auxiliary switch of VCBAuxiliary switch for test positionAuxiliary switch for service positionAnti-pumping relayResistanceBypass of R0Connector of K0 (the internal anti-pumpingfunction will be dismissed if it is cut )Withdrawable Installation for DC ControlSecoVac 15


SecoVac <strong>12</strong>-<strong>24kV</strong>Internal Wiring DiagramOpening circuit2nd opening circuitClose blocking circuitClosing circuitCharging circuitOvercurrentreleaseOvercurrentreleaseOvercurrentreleaseUndervoltagerelease(A phase) (B phase) (C phase)Closing monitor circuitNotes:1.2.3.4.Aux.switch-S1 shown for VCB-mechanism isdischarged.VCB in opening status.The optional components are not included in basicversion if not specified .Auxiliary switch S2 should be bypassed when blockmagnet Y1 is not required.Y1Y2Y3Y4Y7-Y9Y10PMV0-V5Closing block magnetFirst opening releaseClosing releaseUndervoltage releaseIndirect overcurrent release ( optional )Second opening release ( optional )Manual chargingCharging motorRectifier ( V0 & V5 optional )S1S2S3K0R0JP1JS1Auxiliary switch of charging MotorAuxiliary switch of block magnet- Y1Auxiliary switch of VCBAnti-pumping relayResistanceBypass of R0Connector of K0 ( the internal anti-pumpingfunction will be dismissed if it is cut )Fixed Installation for AC ControlOpening circuit2nd opening circuitClose blocking circuitClosing circuitCharging circuitOvercurrentreleaseOvercurrentreleaseOvercurrentreleaseUndervoltagerelease(A phase) (B phase) (C phase)Notes:1.2.3.4.5.Aux.switch-S1 shown for VCB-mechanism isdischarged.VCB in opening status.The optional components are not includerd in basicversion if not specified .Auxiliary switch S2 should be bypassed when blockmagnet Y1 is not required.The connect points in dashed are as should beconnected with positive pole.Y1Y2Y3Y4Y7-Y9Y10PMClosing monitor circuitClosing block magnetFirst opening releaseClosing releaseUndervoltage releaseIndirect overcurrent release ( optional )Second opening release ( optional )Manual chargingCharging motorS1S2S3K0R0JP1JS1Auxiliary switch of charging MotorAuxiliary switch of block magnet- Y1Auxiliary switch of VCBAnti-pumping relayResistanceBypass of R0Connector of K0 ( the internal anti-pumpingfunction will be dismissed if it is cut )Fixed Installation for DC ControlSecoVac 16


Basic type designationRated voltageOperating mechanismRated currentRated short circuitbreaking currentType of control voltageControl voltagePhase-to-phase distanceInstallation modeSecoVac <strong>12</strong>-<strong>24kV</strong>Product TypeSecoVac / -Rated short circuit breaking current (kA): 20, 25, 31.5, 40, 50Rated current (A): 630, <strong>12</strong>50, 1600, 2000, 2500, 3150, 4000Rated voltage (kV): <strong>12</strong>, 24SecoVac <strong>Vacuum</strong> <strong>Circuit</strong> <strong>Breaker</strong>Ordering InformationCoding System of Catalogue NumberSymbol Meaning of the codeSEV T DSEV<strong>12</strong>24T06<strong>12</strong>16202531402025314050AD1<strong>12</strong>2P15 WP21 FP27WWFSecoVacFrom 7.2kV up to <strong>12</strong>kV<strong>24kV</strong>Spring operating mechanismRated current: 630 ARated current: <strong>12</strong>50ARated current: 1600ARated current: 2000ARated current: 2500ARated current: 3150ARated current: 4000ARated short circuit breaking current: 20kARated short circuit breaking current: 25kARated short circuit breaking current: 31.5kARated short circuit breaking current: 40kARated short circuit breaking current: 50kAAC auxiliary control voltageDC auxiliary control voltageRated auxiiary control voltage: 110VRated auxiiary control voltage: 220VPhase-to-phase distance 150mmPhase-to-phase distance 210mmPhase-to-phase distance 275mmWithdrawable installationFixed installationSecoVac 17


SecoVac <strong>12</strong>-<strong>24kV</strong>Checking list for SecoVac OrderCustomer :<strong>Breaker</strong> typeRated voltageRated currentRated short-circuitbreaking currentDistance of Pole (P)Motor-operated (M)*Blocking magnet Y1Shunt releasesONOFF Y2Y3Over-current releasesY7Y8Y9 ( optional )Under-voltage releaseY4 ( optional )Truck blockingY0 ( optional )Anti-pump relay K02 nd Release Y10( optional )Secondary wiringWithdrawable( W type )Fixed( F type )Other itemsProject :Order NO.SecoVacQuantity7.2kV <strong>12</strong>kV <strong>24kV</strong>630A <strong>12</strong>50A 1600A 2000A 2500A 3150A 4000A20kA 25kA 31.5kA 40kA 50kA150mm 210mm 275mmDC220V DC110V AC220V AC110V OtherDC220V DC110V AC220V AC110V OtherDC220V DC110V AC220V AC110VOtherDisabledY7/Y9 ( AC5A ) Y7/Y8/Y9 ( AC5A )DisabledDC220V DC110V AC220V AC110VDisabledDC220V DC110V AC220V AC110V OtherStandard Non-standard ( Attached drawing .NO. :Earthing mode: earthing with copper bar at the bottom of truckearthing with connecter on the sides of truck OtherSecondary wiring: connect with terminal strips on the top of cabinetwith control wiring plugwith control wiring plug installed on the top of cabinetOtherMechanical interlock: Disabledsticking out <strong>12</strong>0mm on the left side of principal axiswith opening release Other( Please attach concerned drawing or data in case any special requests. )1.2.3.)* Blocking magnet Y1: Standard for withdrawable part; optional for fixed part.Prepare dateCheck dateSecoVac 18


GEIndustrialAPO HeadquartersChina23F,Building C,Hi-Tech Building,900 Yishan Road,Shanghai200233Tel: +86 21 2401 3333Fax: +86 21 5423 5080IndonesiaBRI II Tower, 15th Floor Suite 1505Jl. Jendral SudirmanNo. 44-46Jakarta 10210IndonesiaTel: +62 21 5730 429Fax: +62 21 574 7089Australia<strong>12</strong>5-<strong>12</strong>7 Long StreetSmithfield, SydneyNSW 2164AustraliaTel: +61 (0)2 8788 6911Fax: +61 (0)2 9729 0433JapanAkasaka Park Bldg.,5-2-20 Akasaka,Minato-ku, Tokyo 107-61<strong>12</strong>JapanTel: +81 03 5544 6781Fax: +81 03 5544 6760IndiaThe Millenia, Level 6, Tower B, # 1 & 2Murphy Road, UlsoorBangalore - 560 008IndiaTel: +91 80 4143 4000Fax: +91 80 4143 4199MalaysiaSuite 3B-8-3, Block 3B,Leval 8, Plaza Sentral,Jalan Stesen Sentral,Kuala Lumpur Sentral 50470,Kuala Lumpur, Malaysia.Tel: +603 2273 9788Fax: +603 2273 3481Philippines1873 P.Domingo StMakati CityPhilippines <strong>12</strong>07Tel: +63 2 895 7051/59Fax: +63 2 890 8186Thailand1<strong>12</strong>6/2, Vanit Building II16th Floor Room 1603,New Petchburi Road,Makkasan RatchathewiBangkok 10400ThailandTel: +66 2 255 8721Fax: +66 2 255 8733Hongkong15/F, The Lee Gardens,33 Hysan Avenue.Causeway BayTel: +852 62943050Fax: +852 23760013Singapore240 Tanjong Pagar Road,#06-00 GE TowerSingapore 088540Tel: +65 6220 7022Fax: +65 6326 3015VietnamFloor 7 Saigon Centre65 Le Loi StreetDistrict 1 Ho Chi Minh City,VietnamTel: +84 8 914 6490Fax: +84 8 827 8229New ZealandLevel 10, Lurnley House 7 City Road.Auckland.Tel: +64 9 353 6706Fax: +64 9 353 6707Taiwan6F, No. 8 Sec. 3Min-Sheng E. Road.Taipei,Taiwan 10480Tel: +886 2 2183 7000Fax: +886 2 2516 6829Korea3F.,GE Tower,71-3,Cheongdam-dong,Ganam-gu,Seoul 135-100 KoreaTel: +82 2 6201 4505Fax: +82 2 6201 4545This company reserves the right to improvethe products according to the situation.This publication describes the status of theproducts at the time of its issuing and maynot reflect future condition of the product.Publication NO.GE/SV<strong>12</strong>-24/CA/2008/001GE imagination at work