Suction Pressure High ChecklistImproper Installation• Refer to “Installation and Visual InspectionChecklist” on page 104.Discharge Pressure• Discharge pressure is too high, and is affectingsuction pressure, refer to “Discharge PressureHigh Checklist” on page 150.Improper Refrigerant Charge• Overcharged• Wrong type of refrigerant• Non-condensables in systemOther• Non-<strong>Manitowoc</strong> components in system• Hot gas valve leaking• Defective compressor• Water inlet valve leakingSuction Pressure Low ChecklistImproper Installation• Refer to “Installation and Visual InspectionChecklist” on page 104.Discharge Pressure• Discharge pressure is too low, and is affectingsuction pressure, refer to “Freeze Cycle DischargePressure Low Checklist” on page 150.Improper Refrigerant Charge• Undercharged• Wrong type of refrigerantPart Number 80-01111-9 7/10 153