Psychrometric Chart – FRC• 65F – 85F cold aisletemperature• 90% relative humiditymax• 41.9F min dew pointtemp• DX added for extremeweather criteria in tocondition the airwithin acceptableserver conditions• 35F delta T acrossservers allowed tominimize fan arraysfrom (14) to (8)• Also reduced the evappump skid redundancy