Facebook Data Center Design/Operations Improvements by Tom ...
Facebook Data Center Design/Operations Improvements by Tom ... Facebook Data Center Design/Operations Improvements by Tom ...
From Prineville to Forest City-45%air handlinghardware
Psychrometric Chart – PRN1A1B• 65F – 80F cold aisletemperature• 65% relativehumidity max• 41.9F min dew pointtemp• 105F Dry Bulb /70.3F Wet Bulb• Summer: 110ºFDB,70.3ºFWB
- Page 3 and 4: Forest City, NC
- Page 5 and 6: In-rush Current with PSU• Higher
- Page 8 and 9: Lessons Learned - Mechanical
- Page 10 and 11: Lessons Learned• Controls issues
- Page 12 and 13: Next Steps - Mechanical
- Page 16 and 17: Psychrometric Chart - PRN1C1D• 65
- Page 18: Questions?
Psychrometric Chart – PRN1A1B• 65F – 80F cold aisletemperature• 65% relativehumidity max• 41.9F min dew pointtemp• 105F Dry Bulb /70.3F Wet Bulb• Summer: 110ºFDB,70.3ºFWB