Forest City, NC
Lessons Learned - Electrical
In-rush Current with PSU• Higher in-rush current experienced under repeatedpower outage• CB see the high in-rush and trip on GF• Cause due to NTC resistor characteristics• Adjusted setting accordingly to resolve issue
In-rush Current with PSU
Lessons Learned - Mechanical
PUE Update for PrinevillePUE <strong>Data</strong>: Trended each minute; for period 14 Apr, 2011- 15 Jun, 2011
Lessons Learned• Controls issues with a 100% OA economization withdirect evaporative cooling• We found an error in the controls sequence during highhumidity levels within the datacenter that turned a singlepass system into a recirculating system <strong>by</strong> closing theoutside air dampers 100%• Control loop tuning (14) independently controlled AHU lineups has posed challenging issues to controllingtemperature and humidity during large swings betweenday and night during the summer season
Lessons Learned• WUE has not been reported as we are verifyingreadings. The original system wasn’t designed tocalculate WUE as the design were complete in late2009, WUE was created in March of 2011 <strong>by</strong> TheGreen Grid.• A perforated target plate is for improved air distributionwithin the datacenter is in review
Next Steps - Mechanical
<strong>Data</strong>center Basis of <strong>Design</strong> Comparison80ºF inlet85ºF inlet85ºF inlet65% humidity80% humidity90% humidity20ºF ΔT 35ºF ΔT 35ºF ΔTPRN1A1BPRN1C1DFRC1A1B
From Prineville to Forest City-45%air handlinghardware
Psychrometric Chart – PRN1A1B• 65F – 80F cold aisletemperature• 65% relativehumidity max• 41.9F min dew pointtemp• 105F Dry Bulb /70.3F Wet Bulb• Summer: 110ºFDB,70.3ºFWB
Psychrometric Chart – PRN1C1D• 65F – 85F cold aisletemperature• 80% relative humiditymax• 41.9F min dew point temp• 35F delta T acrossservers allowed tominimize fan arrays from(14) to (8)• We reduced the evap pumpskid redundancy from 2Nto N• 105F Dry Bulb / 70.3F
Psychrometric Chart – FRC• 65F – 85F cold aisletemperature• 90% relative humiditymax• 41.9F min dew pointtemp• DX added for extremeweather criteria in tocondition the airwithin acceptableserver conditions• 35F delta T acrossservers allowed tominimize fan arraysfrom (14) to (8)• Also reduced the evappump skid redundancy