PART 3.00EXECUTIONFTWIC-2235June 20093.01 INSTALLATION:A. Install distribution panels in accordance with applicable codes at each location indicatedon the plans. Provide filler plates for unused spaces in the panel. Labeling shall be inaccordance with Section 16010, GENERAL REQUIREMENTS FOR ELECTRICALWORK. Panelboards shall be mounted so that the height to the top of the panelboardshall not exceed 81 inches above the finished floor level. Directories shall be typed toindicate the load served by each circuit and shall be mounted on the inside of the door ina holder with a protective covering. The directory shall be arranged so that the typedentries simulate the circuit breaker position in the panelboard.B. Adjust trip and time delay settings for proper coordination.END OF SECTION16163-4