16120 600 VOLT WIRES AND CABLESFTWIC-2235June 2009PART 1.00GENERAL1.01 WORK INCLUDED:A. Furnish labor, materials, equipment and incidentals necessary to install 600 volt wiresand cables.B. Work Shall Include:1. Wire2. Multi-conductor Cable3. Wiring Connections and Terminations1.02 RELATED WORK COVERED ELSEWHERE:General Requirements for Electrical Work Section 16010Wire Connections and Devices Section 161221.03 QUALITY ASSURANCE:TESTING:Megger test circuits for continuity and ground; verify phasing at connection points. Torque testconductor connections and terminations to the Manufacturer's recommended values.1.04 SUBMITTALS:Submittals shall be in accordance with Section 01300, SUBMITTALS, and shall include:Low Voltage WireGround WireModular WiringMulti-conductor Cable1.05 STANDARDS AND REFERENCES:Refer to Section 16010, GENERAL REQUIREMENTS FOR ELECTRICAL WORK, for allstandards which apply to this section.1.06 DELIVERY, HANDLING AND STORAGE:Deliver cable and wire to the project in the original packages. Conductors with damagedinsulation shall not be permitted.16120-1