FTWIC-2235June, 20093.03 FIELD QUALITY CONTROL:A. Ceilings shall be installed to a tolerance of 1/8" in 12'-0" in level and straightnessvariation shall not exceed 1/360 of span length.B. Defective tile and suspension system will be replaced. Defects to include:1. System which are not level.2. Warping or sagging of tile.3. Loosening of adhesive applied tile.4. Loosening of hanger wires.3.04 CLEAN AND ADJUST:A. Prior to final inspection, replace broken or damaged tile, or tile, which has chippedcorners or edges, exposed to view. Align tile and replace any having an improper fit inthe grid system.B. Clean soiled or discolored units. Remove hand prints or smudges. Clean or replacesmudged tile around air conditioning outlets.END OF SECTION09509-5